GE Multilin
C70 Capacitor Bank Protection and Control System
5-221
5 SETTINGS
5.7 CONTROL ELEMENTS
5
Figure 5–98: CAPACITOR BANK CONTROL SCHEME LOGIC
FLEXLOGIC OPERAND
CAP 1 IN LOCAL
CAP 1 IN REMOTE
S
R
SETTINGS
CAP 1 SET LOCAL 1
OR
OR
CAP 1 SET REMOTE 1
CAP 1 SET REMOTE 2
CAP 1 LCL CTRL EN
CAP 1 RMT CTRL EN
CAP 1 AUTO CTRL EN
CAP 1 MAN CTRL EN
AND
AND
AND
OR
OR
S
R
FLEXLOGIC OPERAND
CAP 1 IN AUTO
CAP 1 IN MAN
CAP 1 LCL SET AUTO
CAP 1 RMT SET AUTO
CAP 1 LCL SET MAN
CAP 1 RMT SET MAN
AND
AND
AND
OR
SETTINGS
CAP 1 LOCAL OPEN
CAP 1 REMOTE OPEN
CAP 1 TRIP 1
CAP 1 TRIP 2
CAP 1 TRIP 3
CAP 1 TRIP 4
CAP 1 TRIP 5
CAP 1 TRIP 6
CAP 1 AUTO OPEN
SETTINGS
AND
AND
AND
AND
SETTINGS
CAP 1 LOCAL CLOSE
CAP 1 REMOTE CLOSE
CAP 1 AUTO CLOSE
CAP 1 CLOSE SEAL-IN DELAY
SETTINGS
0
OR
AND
CAP 1 TRIP SEAL-IN DELAY
SETTINGS
0
t
PKP
t
PKP
SETTINGS
CAP 1 BKR OPEN 52b
CAP 1 BKR CLSD 52a
AND
CAP 1 DISCHARGE TIME:
SETTINGS
t
DPO
0
OR
OR
AND
SETTINGS
CAP 1 BKR CLOSE BLK
FLEXLOGIC OPERAND
CAP 1 BKR TRIP
FLEXLOGIC OPERAND
CAP 1 BKR CLOSE
SETTINGS
CAP 1 CTRL FUNCTION
Enabled = 1
AND
AND
Reset Dominant
Non-Volatile Latch
Reset Dominant
Non-Volatile Latch
FLEXLOGIC OPERAND
CAP 1 DISCHARGING
FLEXANALOG
CAP 1 DISCHRG TIME
seconds remaining till
closing is enabled
Reset
SETTINGS
OR
CAP 1 SWITCH TO MANUAL
ON TRIP:
AND
Yes = 1
SETTING
CAP 1 1 CLS OVERRIDE:
Off = 0
OR
SETTINGS
SETTINGS
SETTINGS
AND
CAP 1 SET LOCAL 2
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
OFF = 0
834740A1.DWG
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...