GE Multilin
C70 Capacitor Bank Protection and Control System
5-41
5 SETTINGS
5.2 PRODUCT SETUP
5
l) IEC 61850 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
The C70 Capacitor Bank Protection and Control System is provided with optional IEC 61850 communica-
tions capability. This feature is specified as a software option at the time of ordering. See the
Order Codes
section in chapter 2 for details.
IEC 61850 messaging can form part of protection schemes. Consider 61850 settings with the same criticality as
protection element settings. To ensure reliable performance of protection schemes utilizing 61850 messaging, it
can be desirable to route 61850 traffic on a separate port from SCADA communications, or to use redundant, inde-
pendent ports, and a high speed network recovery method, such as PRP.
The C70 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported
over two protocol stacks: TCP/IP over Ethernet. The C70 operates as an IEC 61850 server. The
Remote Inputs and Out-
puts
section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception.
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
The main transmission menu is shown below:
IEC 61850 PROTOCOL
GSSE / GOOSE
CONFIGURATION
MESSAGE
SERVER
CONFIGURATION
MESSAGE
IEC 61850 LOGICAL
NODE NAME PREFIXES
MESSAGE
MMXU DEADBANDS
MESSAGE
GGIO1 STATUS
CONFIGURATION
MESSAGE
GGIO2 CONTROL
CONFIGURATION
MESSAGE
GGIO4 ANALOG
CONFIGURATION
MESSAGE
GGIO5 UINTEGER
CONFIGURATION
MESSAGE
REPORT CONTROL
CONFIGURATION
MESSAGE
XCBR
CONFIGURATION
MESSAGE
XSWI
CONFIGURATION
GSSE / GOOSE
CONFIGURATION
TRANSMISSION
MESSAGE
RECEPTION
NOTE
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...