GE Multilin
C70 Capacitor Bank Protection and Control System
5-17
5 SETTINGS
5.2 PRODUCT SETUP
5
General Security Settings
Security Alarm Settings
SETTING NAME
DESCRIPTION
MIN
MAX
DEFAULT UNITS MINIMUM
PERMISSION
Session Lockout
Number of failed authentications before the
device blocks subsequent authentication
attempts for the lockout period
0 (lockout
disabled)
99
3
-
Administrator
Session Lockout
Period
The period in minutes that a user is prevented
from logging in after being locked out
0 (no period) 9999
3
min
Administrator
Syslog Server IP
Address
The IP address of the target Syslog server to
which all security events are transmitted
0.0.0.0
223.255.
255.254
0.0.0.0
-
Administrator
Syslog Server Port
Number
The UDP port number of the target syslog server
to which all security events are transmitted
1
65535
514
-
Administrator
Device
Authentication
When enabled, local device authentication with
roles is allowed. When disabled, the UR only
authenticates to the AAA server (RADIUS).
NOTE:
Administrator and Supervisor (if still
enabled) remain active even after device
authentication is disabled. The only permission
for local Administrator is to re-enable device
authentication when device authentication is
disabled. To re-enable device authentication, the
Supervisor unlocks the device for setting
changes, and then the Administrator can re-
enable device authentication.
Disabled
Enabled
Enabled
-
Administrator
Firmware Locked
Indicates if the device receives firmware
upgrades. If Yes and the firmware upgrade
attempt is made, the device denies the upgrade
and displays an error message that the lock is
set. On each firmware upgrade, this setting goes
back to the default.
No
Yes
Yes
-
Administrator
Factory Service
Mode
When enabled (checkbox selected), the device
can go into factory service mode. To enable,
Supervisor authentication is necessary.
Disabled
Enabled
Disabled
-
Supervisor
(Administrator
when Supervisor
is disabled)
Restore to Defaults Sets the device to factory defaults
No
Yes
No
-
Administrator
Supervisor role
When enabled (checkbox selected), the
Supervisor role is active. To enable,
Administrator authentication is necessary. When
disabled, the Supervisor role is inactive. To
disable, Supervisor authentication is necessary.
Disabled
Enabled
Enabled
-
Administrator to
enable and
Supervisor to
disable
RADIUS user
names
Ensure that RADIUS user names are not the
same as local/device role names
See RADIUS
server
documents
See
RADIUS
server
documents
-
Administrator
Password
Local/device roles except for Observer are
password-protected. All RADIUS users are
password-protected.
See the
Password
Requirement
s
section
See the
following
password
section for
requireme
nts
Change
Me1#
Text
The specified role
and Administrator,
except for
Supervisor, where
it is only itself
SETTING NAME
DESCRIPTION / DETAILS
MIN
MAX
DEFAULT UNITS
MINIMUM
PERMISSIONS
Failed
Authentications
A threshold number indicating when an alarm is
set off to indicate too many failed authentication
attempts
0
(disabled)
99
3
-
Administrator
Firmware lock
A Boolean value indicating if the device can
receive a firmware upgrade. If Yes and a
firmware upgrade attempt is made, the device
alarm activates. If No the device alarm does not
activate. On each firmware upgrade this setting
goes back to the default.
No
Yes
Yes
-
Administrator
Settings lock
A Boolean value indicating if the device can
accept any settings changes. If Yes and a
settings change attempt is made, the device
alarm activates. If No, the device alarm does not
activate.
No
Yes
Yes
-
Supervisor
(Administrator if
Supervisor has
been disabled)
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...