GE Multilin
C70 Capacitor Bank Protection and Control System
B-67
APPENDIX B
B.4 MEMORY MAPPING
B
CAD1
Direct Input/Output Channel 1 CRC Alarm Message Count
100 to 10000
---
1
F001
600
CAD2
Direct Input/Output Channel 1 CRC Alarm Threshold
1 to 1000
---
1
F001
10
CAD3
Direct Input/Output Channel 1 CRC Alarm Events
0 to 1
---
1
F102
0 (Disabled)
CAD4
Reserved (4 items)
1 to 1000
---
1
F001
10
CAD8
Direct Input/Output Channel 2 CRC Alarm Function
0 to 1
---
1
F102
0 (Disabled)
CAD9
Direct Input/Output Channel 2 CRC Alarm Message Count
100 to 10000
---
1
F001
600
CADA
Direct Input/Output Channel 2 CRC Alarm Threshold
1 to 1000
---
1
F001
10
CADB
Direct Input/Output Channel 2 CRC Alarm Events
0 to 1
---
1
F102
0 (Disabled)
CADC
Reserved (4 items)
1 to 1000
---
1
F001
10
CAE0
Direct Input/Output Ch 1 Unreturned Messages Alarm
Function
0 to 1
---
1
F102
0 (Disabled)
CAE1
Direct Input/Output Ch 1 Unreturned Messages Alarm Msg
Count
100 to 10000
---
1
F001
600
CAE2
Direct Input/Output Ch 1 Unreturned Messages Alarm
Threshold
1 to 1000
---
1
F001
10
CAE3
Direct Input/Output Ch 1 Unreturned Messages Alarm
Events
0 to 1
---
1
F102
0 (Disabled)
CAE4
Reserved (4 items)
1 to 1000
---
1
F001
10
CAE8
Direct Input/Output Ch 2 Unreturned Messages Alarm
Function
0 to 1
---
1
F102
0 (Disabled)
CAE9
Direct Input/Output Ch 2 Unreturned Messages Alarm Msg
Count
100 to 10000
---
1
F001
600
CAEA
Direct Input/Output Ch 2 Unreturned Messages Alarm
Threshold
1 to 1000
---
1
F001
10
CAEB
Direct Input/Output Channel 2 Unreturned Messages Alarm
Events
0 to 1
---
1
F102
0 (Disabled)
CAEC
Reserved (4 items)
1 to 1000
---
1
F001
10
Remote Devices (Read/Write Setting) (16 modules)
CB00
Remote Device 1 GSSE/GOOSE Application ID (GOID)
---
---
---
F209
“Remote Device
1“
CB21
Remote Device 1 GOOSE Ethernet APPID
0 to 16383
---
1
F001
0
CB22
Remote Device 1 GOOSE Dataset
0 to 16
---
1
F184
0 (Fixed)
CB23
Remote Device 1 in PMU Scheme
0 to 1
---
1
F126
0 (No)
CB24
Reserved
0 to 3
---
1
F626
0 (None)
CB25
...Repeated for Device 2
CB4A
...Repeated for Device 3
CB6F
...Repeated for Device 4
CB94
...Repeated for Device 5
CBB9
...Repeated for Device 6
CBDE
...Repeated for Device 7
CC03
...Repeated for Device 8
CC28
...Repeated for Device 9
CC4D
...Repeated for Device 10
CC72
...Repeated for Device 11
CC97
...Repeated for Device 12
CCBC
...Repeated for Device 13
CCE1
...Repeated for Device 14
CD06
...Repeated for Device 15
CD2B
...Repeated for Device 16
Remote Inputs (Read/Write Setting) (32 modules)
CFA0
Remote Input 1 Device
1 to 32
---
1
F001
1
CFA1
Remote Input 1 Bit Pair
0 to 96
---
1
F156
0 (None)
CFA2
Remote Input 1 Default State
0 to 3
---
1
F086
0 (Off)
CFA3
Remote Input 1 Events
0 to 1
---
1
F102
0 (Disabled)
CFA4
Remote Input 1 Name
1 to 64
---
1
F205
“Rem Ip 1”
CFAA
...Repeated for Remote Input 2
CFB4
...Repeated for Remote Input 3
Table B–10: MODBUS MEMORY MAP (Sheet 59 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...