B-18
C70 Capacitor Bank Protection and Control System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
1FB3
Source 1 Vc Harmonics - 2nd to 25th (24 items)
0 to 99.9
---
0.1
F001
0
1FCB
...Repeated for Source 2
2016
...Repeated for Source 3
2061
...Repeated for Source 4
20AC
...Repeated for Source 5
20F7
...Repeated for Source 6
Breaker Flashover (Read/Write Setting) (1 module)
2196
Breaker Flashover 1 Function
0 to 1
---
1
F102
0 (Disabled)
2197
Breaker Flashover 1 Side 1 Source
0 to 5
---
1
F167
0 (SRC 1)
2198
Breaker Flashover 1 Side 2 Source
0 to 6
---
1
F211
0 (None)
2199
Breaker Flashover 1 Status Closed A
0 to 4294967295
---
1
F300
0
219B
Breaker Flashover 1 Status Closed B
0 to 4294967295
---
1
F300
0
219D
Breaker Flashover 1 Status Closed C
0 to 4294967295
---
1
F300
0
219F
Breaker Flashover 1 Voltage Pickup Level
0 to 1.5
pu
0.001
F001
850
21A0
Breaker Flashover 1 Voltage Difference Pickup Level
0 to 100000
V
1
F060
1000
21A2
Breaker Flashover 1 Current Pickup Level
0 to 1.5
pu
0.001
F001
600
21A3
Breaker Flashover 1 Pickup Delay
0 to 65.535
s
0.001
F001
100
21A4
Breaker Flashover 1 Supervision Phase A
0 to 4294967295
---
1
F300
0
21A6
Breaker Flashover 1 Supervision Phase B
0 to 4294967295
---
1
F300
0
21A8
Breaker Flashover 1 Supervision Phase C
0 to 4294967295
---
1
F300
0
21AA
Breaker Flashover 1 Block
0 to 4294967295
---
1
F300
0
21AC
Breaker Flashover 1 Events
0 to 1
---
1
F102
0 (Disabled)
21AD
Breaker Flashover 1 Target
0 to 2
---
1
F109
0 (Self-Reset)
21AE
Reserved (4 items)
---
---
---
F001
0
Passwords Unauthorized Access (Read/Write Command)
2230
Reset Unauthorized Access
0 to 1
---
1
F126
0 (No)
Field Unit Raw Data Settings (Read/Write Setting)
2460
Field Raw Data Port
0 to 7
---
1
F244
6 (H1a)
2461
Field Raw Data Freeze
0 to 1
---
1
F102
0 (Disabled)
Remote Double-Point Status Inputs (Read/Write Setting Registers) (5 modules)
2540
Remote Double-point Status Input 1 Device
1 to 32
---
1
F001
1
2541
Remote Double-point Status Input 1 Item
0 to 64
---
1
F606
0 (None)
2542
Remote Double-point Status Input 1 Name
1 to 64
---
1
F205
"RemDPS Ip 1"
2548
Remote Double-point Status Input 1 Events
0 to 1
---
1
F102
0 (Disabled)
2549
... Repeated for Remote Double-point Status Input 2
2552
... Repeated for Remote Double-point Status Input 3
255B
... Repeated for Remote Double-point Status Input 4
2564
... Repeated for Remote Double-point Status Input 5
IEC 61850 GGIO5 Configuration (Read/Write Setting Registers) (16 modules)
26D0
IEC 61850 GGIO5 uinteger Input 1 Operand
---
---
---
F612
0
26D1
IEC 61850 GGIO5 uinteger Input 2 Operand
---
---
---
F612
0
26D2
IEC 61850 GGIO5 uinteger Input 3 Operand
---
---
---
F612
0
26D3
IEC 61850 GGIO5 uinteger Input 4 Operand
---
---
---
F612
0
26D4
IEC 61850 GGIO5 uinteger Input 5 Operand
---
---
---
F612
0
26D5
IEC 61850 GGIO5 uinteger Input 6 Operand
---
---
---
F612
0
26D6
IEC 61850 GGIO5 uinteger Input 7 Operand
---
---
---
F612
0
26D7
IEC 61850 GGIO5 uinteger Input 8 Operand
---
---
---
F612
0
26D8
IEC 61850 GGIO5 uinteger Input 9 Operand
---
---
---
F612
0
26D9
IEC 61850 GGIO5 uinteger Input 10 Operand
---
---
---
F612
0
26DA
IEC 61850 GGIO5 uinteger Input 11 Operand
---
---
---
F612
0
26DB
IEC 61850 GGIO5 uinteger Input 12 Operand
---
---
---
F612
0
26DC
IEC 61850 GGIO5 uinteger Input 13 Operand
---
---
---
F612
0
26DD
IEC 61850 GGIO5 uinteger Input 14 Operand
---
---
---
F612
0
26DE
IEC 61850 GGIO5 uinteger Input 15 Operand
---
---
---
F612
0
Table B–10: MODBUS MEMORY MAP (Sheet 10 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...