GE Multilin
C70 Capacitor Bank Protection and Control System
5-207
5 SETTINGS
5.7 CONTROL ELEMENTS
5
Figure 5–89: TRIP BUS FIELDS IN THE PROTECTION SUMMARY
The following settings are available.
•
TRIP BUS 1 BLOCK
: The trip bus output is blocked when the operand assigned to this setting is asserted.
•
TRIP BUS 1 PICKUP DELAY
: This setting specifies a time delay to produce an output depending on how output is
used.
•
TRIP BUS 1 RESET DELAY
: This setting specifies a time delay to reset an output command. The time delay should be
set long enough to allow the breaker or contactor to perform a required action.
•
TRIP BUS 1 INPUT 1
to
TRIP BUS 1 INPUT 16
: These settings select a FlexLogic operand to be assigned as an input
to the trip bus.
•
TRIP BUS 1 LATCHING
: This setting enables or disables latching of the trip bus output. This is typically used when
lockout is required or user acknowledgement of the relay response is required.
•
TRIP BUS 1 RESET
: The trip bus output is reset when the operand assigned to this setting is asserted. Note that the
RESET OP
operand is pre-wired to the reset gate of the latch, As such, a reset command the front panel interface or via
communications will reset the trip bus output.
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...