5-28
C70 Capacitor Bank Protection and Control System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
Single LAN, No Redundancy
The topology shown in the following figure allows communications to SCADA, local configuration/monitoring through
EnerVista, and access to the public network shared on the same LAN. No redundancy is provided.
Figure 5–4: NETWORK CONFIGURATION FOR SINGLE LAN
Multiple LANS, with Redundancy
The topology in the following figure provides local configuration/monitoring through EnerVista software and access to the
public network shared on LAN1, to which port 1 (P1) is connected. There is no redundancy provided on LAN1. Communica-
tions to SCADA is provided through LAN2. P2 and P3 are connected to LAN2, where P2 is the primary channel and P3 is
the redundant channel. In this configuration, P3 uses the IP and MAC address of P2.
Figure 5–5: MULTIPLE LANS, WITH REDUNDANCY
EnerVista Software
ML3000
Public Network
SCADA
UR
P2
P3
LAN1
P1
IP1/
MAC1
859708A2.vsd
P3
IP2/
MAC2
EnerVista Software
ML3000
Public Network
SCADA
UR
P1
IP1/
MAC1
P2
IP2/
MAC2
ML3000
ML3000
Redundancy mode
LAN1
LAN2
LAN2
859709A4.vsd