GE Multilin
C70 Capacitor Bank Protection and Control System
B-49
APPENDIX B
B.4 MEMORY MAPPING
B
955C
...Repeated for Direct Input/Output 30
9568
...Repeated for Direct Input/Output 31
9574
...Repeated for Direct Input/Output 32
IEC 61850 Received Integers (Read/Write Setting) (16 modules)
98A0
IEC 61850 GOOSE uinteger 1 Default Value
0 to 429496295
---
1
F003
1000
98A2
IEC 61850 GOOSE uinteger Input 1 Mode
0 to 1
---
1
F491
0 (Default
Value)
98A3
...Repeated for IEC61850 GOOSE uinteger 2
98A6
...Repeated for IEC61850 GOOSE uinteger 3
98A9
...Repeated for IEC61850 GOOSE uinteger 4
98AC
...Repeated for IEC61850 GOOSE uinteger 5
98AF
...Repeated for IEC61850 GOOSE uinteger 6
98B2
...Repeated for IEC61850 GOOSE uinteger 7
98B5
...Repeated for IEC61850 GOOSE uinteger 8
98B8
...Repeated for IEC61850 GOOSE uinteger 9
98BB
...Repeated for IEC61850 GOOSE uinteger 10
98BE
...Repeated for IEC61850 GOOSE uinteger 11
98C1
...Repeated for IEC61850 GOOSE uinteger 12
98C4
...Repeated for IEC61850 GOOSE uinteger 13
98C7
...Repeated for IEC61850 GOOSE uinteger 14
98CA
...Repeated for IEC61850 GOOSE uinteger 15
98CD
...Repeated for IEC61850 GOOSE uinteger 16
FlexElement Actual Values (Read Only) (16 modules)
9900
FlexElement 1 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9902
FlexElement 2 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9904
FlexElement 3 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9906
FlexElement 4 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9908
FlexElement 5 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
990A
FlexElement 6 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
990C
FlexElement 7 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
990E
FlexElement 8 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9910
FlexElement 9 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9912
FlexElement 10 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9914
FlexElement 11 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9916
FlexElement 12 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9918
FlexElement 13 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
991A
FlexElement 14 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
991C
FlexElement 15 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
991E
FlexElement 16 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
Breaker Restrike (Read/Write Setting) (3 modules)
9930
Breaker Restrike 1 Function
0 to 1
---
1
F102
0 (Disabled)
9931
Breaker Restrike 1 Block
0 to 4294967295
---
1
F300
0
9933
Breaker Restrike 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
9934
Breaker Restrike 1 Pickup
0.10 to 2.00
pu
0.01
F001
50
9935
Breaker Restrike 1 Reset Delay
0 to 65.535
s
0.001
F001
100
9936
Breaker Restrike 1 HF Detect
0 to 1
---
1
F102
1 (Enabled)
9937
Breaker Restrike 1 Breaker Open
0 to 4294967295
---
1
F300
0
9939
Breaker Restrike 1 Open Command
0 to 4294967295
---
1
F300
0
993B
Breaker Restrike 1 Close Command
0 to 4294967295
---
1
F300
0
993D
Breaker Restrike 1 Target
0 to 2
---
1
F109
0 (Self-reset)
993E
Breaker Restrike 1 Events
0 to 1
---
1
F102
0 (Disabled)
993F
Reserved (2 items)
---
---
---
F002
0
9941
...Repeated for Breaker Restrike 2
9952
...Repeated for Breaker Restrike 3
Table B–10: MODBUS MEMORY MAP (Sheet 41 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...