C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
APPENDIX C
C
3.
The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and
name for the URS (UR-series relay settings) file.
If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set-
tings file for each IED.
4.
After the URS file is created, modify any settings (if required).
5.
To update the relay with the new settings, right-click on the settings file in the settings tree and select the
Write Set-
tings File to Device
item.
6.
The software will prompt for the target device. Select the target device from the list provided and click
Send
. The new
settings will be updated to the selected device.