GE Multilin
C70 Capacitor Bank Protection and Control System
4-11
4 HUMAN INTERFACES
4.2 EXTENDED ENERVISTA UR SETUP FEATURES
4
The following window is displayed.
Figure 4–10: TYPICAL SETTINGS FILE PROPERTIES WINDOW
3.
Enter the serial number of the C70 device to lock to the settings file in the
Serial # Lock
field.
The settings file and corresponding secure FlexLogic equations are now locked to the C70 device specified by the serial
number.
4.2.3 SETTINGS FILE TRACEABILITY
A traceability feature for settings files allows the user to quickly determine if the settings in a C70 device have been
changed since the time of installation from a settings file. When a settings file is transferred to a C70 device, the date, time,
and serial number of the C70 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor-
mation can be compared with the C70 actual values at any later date to determine if security has been compromised.
The traceability information is only included in the settings file if a complete settings file is either transferred to the C70
device or obtained from the C70 device. Any partial settings transfers by way of drag and drop do not add the traceability
information to the settings file.
Figure 4–11: SETTINGS FILE TRACEABILITY MECHANISM
With respect to the above diagram, the traceability feature is used as follows.
2
The serial number and last setting change date
are stored in the UR-series device.
The serial number of the UR-series device and the file transfer
date are added to the setting file when setting files
are transferred to the device.
842864A2.CDR
Compare transfer dates in the setting file and the
UR-series device to determine if security
has been compromised.
1
SETTING FILE TRANSFERRED
TO UR-SERIES DEVICE
SERIAL NUMBER AND TRANSFER DATE
SENT BACK TO ENERVISTA AND
ADDED TO SETTING FILE.
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...