5 SETTINGS
5.7 CONTROL ELEMENTS
5
To ensure element accuracy for high overcurrent conditions, the maximum value of I/(k x I
B
) is limited to 8, even when real-
istically it is exceeding this value.
The reset time of the thermal overload protection element is also time delayed using following formula:
(EQ 5.23)
In the above equation,
•
τ
rst
= thermal protection trip time constant
•
T
min
is a minimum reset time setting
Figure 5–112: IEC 255-8 SAMPLE OPERATE AND RESET CURVES
The thermal overload protection element estimates accumulated thermal energy
E
using the following equations calculated
each power cycle. When current is greater than the pickup level,
I
n
>
k
×
I
B
, element starts increasing the thermal energy:
(EQ 5.24)
t
rst
τ
rst
kI
B
(
)
2
I
2
kI
B
(
)
2
–
-----------------------------
ln
×
T
min
+
=
0.1
1
10
100
I / Ipkp
t (min)
0.01
0.1
1
10
100
τ
= 30
rst
τ
= 30
op
T
= 10
min
827724A1.CDR
E
n
E
n
1
–
t
Δ
t
op In
( )
---------------
+
=