GE Multilin
C70 Capacitor Bank Protection and Control System
5-51
5 SETTINGS
5.2 PRODUCT SETUP
5
The GGIO1 status configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GGIO1 STATUS CONFIGURATION
The
NUMBER OF STATUS POINTS IN GGIO1
setting specifies the number of “Ind” (single point status indications) that are
instantiated in the GGIO1 logical node. Changes to the
NUMBER OF STATUS POINTS IN GGIO1
setting will not take effect until
the C70 is restarted.
The GGIO2 control configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GGIO2 CONTROL CONFIGURATION
GGIO2 CF SPSCO 1(64)
The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0”
(status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the C70
virtual inputs.
The GGIO4 analog configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GGIO4 ANALOG CONFIGURATION
The
NUMBER OF ANALOG POINTS
setting determines how many analog data points will exist in GGIO4. When this value is
changed, the C70 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newly
configured number of analog points.
GGIO1 STATUS
CONFIGURATION
NUMBER OF STATUS
POINTS IN GGIO1: 8
Range: 8 to 128 in steps of 8
MESSAGE
GGIO1 INDICATION
1
Off
Range: FlexLogic operand
MESSAGE
GGIO1 INDICATION
2
Off
Range: FlexLogic operand
MESSAGE
GGIO1 INDICATION
3
Off
Range: FlexLogic operand
↓
MESSAGE
GGIO1 INDICATION 128
Off
Range: FlexLogic operand
GGIO2 CF SPCSO 1
GGIO2 CF SPCSO 1
CTLMODEL: 1
Range: 0, 1, or 2
GGIO4 ANALOG
CONFIGURATION
NUMBER OF ANALOG
POINTS IN GGIO4:
8
Range: 4 to 32 in steps of 4
MESSAGE
GGIO4 ANALOG 1
MEASURED VALUE
MESSAGE
GGIO4 ANALOG 2
MEASURED VALUE
MESSAGE
GGIO4 ANALOG 3
MEASURED VALUE
↓
MESSAGE
GGIO4 ANALOG 32
MEASURED VALUE
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...