D.1 IEC 60870-5-103
D
<251> Write entry aborted
Selection of standard information numbers in control direction
System functions in control direction
INF Semantics
<0> Initiation of general interrogation
<0> Time synchronization
General commands in control direction
INF Semantics
<16> Auto-recloser on/off
<17> Teleprotection on/off
<18> Protection on/off
<19> LED reset
<23> Activate characteristic 1
<24> Activate characteristic 2
<25> Activate characteristic 3
<26> Activate characteristic 4
Generic functions in control direction
INF Semantics
<240> Read headings of all defined groups
<241> Read values or attributes of all entries of one group
<243> Read directory of a single entry
<244> Read value or attribute of a single entry
<245> General interrogation of generic data
<248> Write entry
<249> Write entry with confirmation
<250> Write entry with execution
<251> Write entry abort
Basic application functions
Test mode
Blocking of monitor direction
Disturbance data
Generic services
Private data
Miscellaneous
MEASURAND
MAX MVAL = TIMES RATED VALUE
1,2
OR
2,4
Current L
1
Current L
2
Current L
3
Voltage L
1-E
Voltage L
2-E
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...