GE Multilin
C70 Capacitor Bank Protection and Control System
B-21
APPENDIX B
B.4 MEMORY MAPPING
B
332C
Syslog Server IP Address
0 to 4294967295
---
1
F003
0
332E
Syslog Server Port Number
1 to 65535
---
1
F001
514
Security Supervisory (Read/Write Setting)
3331
Device Authentication Enable
0 to 1
---
1
F126
1 (Yes)
3332
Supervisor Role Enable
0 to 1
---
1
F102
0 (Disabled)
3333
Lock Relay
0 to 1
---
1
F102
0 (Disabled)
3334
Factory Service Mode Enable
0 to 1
---
1
F102
0 (Disabled)
3335
Failed Authentication Alarm Enable
0 to 1
---
1
F102
1 (Enabled)
3336
Firmware Lock Alarm
0 to 1
---
1
F102
1 (Enabled)
3337
Settings Lock Alarm
0 to 1
---
1
F102
1 (Enabled)
3338
Bypass Access
0 to 3
---
1
F628
0 (Disabled)
333A
Serial Inactivity Timeout
1 to 9999
---
1
F001
1
Security Command (Read/Write Command)
3350
Operator Logoff
0 to 1
---
1
F126
0 (No)
3351
Engineer Logoff
0 to 1
---
1
F126
0 (No)
3352
Administrator Logoff
0 to 1
---
1
F126
0 (No)
3353
Clear Security Data
0 to 1
---
1
F126
0 (No)
Security Reserved Modbus Registers (Read/Write)
3360
Address 0x3360 reserved for serial login (20 items)
0 to 9999
---
1
F001
3
3374
Address 0x3374 reserved for serial logout
0 to 9999
---
1
F001
3
Security Reserved Modbus Registers (Read Only)
3375
Address 0x3374 reserved for serial logout
0 to 5
---
1
F617
3 (Engineer)
Event Recorder (Read Only)
3400
Events Since Last Clear
0 to 4294967295
---
1
F003
0
3402
Number of Available Events
0 to 4294967295
---
1
F003
0
3404
Event Recorder Last Cleared Date
0 to 4294967295
---
1
F050
0
Event Recorder Commands (Read/Write Command)
3406
Event Recorder Clear Command
0 to 1
---
1
F126
0 (No)
Neutral Current Unbalance Commands and Actual Values (Read/Write Unless Noted) (3 modules)
3410
Neutral Current Unbalance Automatic Setting Function
0 to 2
---
1
F092
0 (Disabled)
3411
Neutral Current Unbalance Apply Magnitude
0 to 1
---
1
F126
0 (No)
3412
Neutral Current Unbalance Apply Angle
0 to 1
---
1
F126
0 (No)
3413
60N Apply Magnitude Actual Value (Read Only)
0 to 0.1500
---
0.0001
F003
0
3415
60N Apply Angle Actual Value (Read Only)
0 to 359
degrees
1
F003
0
3417
...Repeated for Neutral Current Unbalance 2
341E
...Repeated for Neutral Current Unbalance 3
Neutral Voltage Unbalance Commands and Actual Values (Read/Write Unless Noted) (3 modules)
3430
Neutral Voltage Unbalance Automatic Setting Function
0 to 2
---
1
F092
0 (Disabled)
3431
59NU XA/XB Ratio Actual Value (Read Only)
0 to 9.9999
---
0.0001
F003
0
3433
Neutral Voltage Unbalance Auto-set XA/XB Ratio
0 to 1
---
1
F126
0 (No)
3434
59NU XA/XC Ratio Actual Value (Read Only)
0 to 9.9999
---
0.0001
F003
0
3436
Neutral Voltage Unbalance Auto-set XA/XC Ratio
0 to 1
---
1
F126
0 (No)
3437
...Repeated for Neutral Voltage Unbalance 2
343E
...Repeated for Neutral Voltage Unbalance 3
Phase Current Unbalance Commands and Actual Values (Read/Write Unless Noted) (3 modules)
3450
Phase Current Unbalance Automatic Setting Function
0 to 2
---
1
F092
0 (Disabled)
3451
Phase Current Unbalance Ka Actual Value (Read Only)
–0.1000 to 0.1000
---
0.0001
F004
0
3453
Phase Current Unbalance Auto-set Ka
0 to 1
---
1
F126
0 (No)
3454
Phase Current Unbalance Kb Actual Value (Read Only)
–0.1000 to 0.1000
---
0.0001
F004
0
3456
Phase Current Unbalance Auto-set Kb
0 to 1
---
1
F126
0 (No)
3457
Phase Current Unbalance Kc Actual Value (Read Only)
–0.1000 to 0.1000
---
0.0001
F004
0
3459
Phase Current Unbalance Auto-set Kc
0 to 1
---
1
F126
0 (No)
345A
...Repeated for Phase Current Unbalance 2
3464
...Repeated for Phase Current Unbalance 3
Table B–10: MODBUS MEMORY MAP (Sheet 13 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...