5-148
C70 Capacitor Bank Protection and Control System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
Figure 5–54: SINGLE-POLE BREAKER FAILURE, INITIATE
AND
OR
OR
OR
AND
OR
OR
OR
OR
OR
OR
AND
AND
AND
AND
AND
AND
Seal-in path
Seal-in path
Seal-in path
to breaker failure
single-pole logic sheet 3
Function
SETTINGS
Enabled = 1
Block
Off = 0
Phase A Initiate
SETTING
Off = 0
Phase B Initiate
SETTING
Off = 0
Three-Pole Initiate
SETTING
Off = 0
Use Seal-In
SETTING
Yes = 1
Use Amp Supervision
SETTING
Yes = 1
Phase C Initiate
SETTING
Off = 0
SETTING
RUN
IC
Pickup
RUN
IA Pickup
RUN
IB
Pickup
Initiated phase A
to breaker failure
single-pole logic sheet 2
BKR FAIL 1 RETRIP A
FLEXLOGIC OPERAND
Initiated
to breaker failure
single-pole logic sheet 2
Phase Current
Supervision Pickup
Source
SETTING
IA
IB
IC
SETTING
Initiated phase B
to breaker failure
single-pole logic sheet 2
BKR FAIL 1 RETRIP B
FLEXLOGIC OPERAND
Initiated phase C
to breaker failure
single-pole logic sheet 2
BKR FAIL 1 RETRIP C
FLEXLOGIC OPERAND
OR
834013A3.CDR
IA
IB
IC
OR
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...