9-6
C70 Capacitor Bank Protection and Control System
GE Multilin
9.3 PROTECTION METHODS FOR CAPACITOR BANKS
9 APPLICATION OF SETTINGS
9
The following figure illustrates a single capacitor bank, ungrounded, with no tap available. In this case, a single CT/VT mod-
ule is required.
Figure 9–5: SINGLE BANK, UNGROUNDED, NO TAP AVAILABLE
The following figure illustrates a single capacitor bank, ungrounded, with a tap. In this case, two CT/VT modules are
required.
Figure 9–6: SINGLE BANK, UNGROUNDED, WITH A TAP
F1-3
F5-7
F8
50P
51P
59B
59NU
51N
C70 CAPACITOR BANK RELAY
F4
spar
es
834757A1.CDR
F1-3
F5-7
F8
50P
51P
59B
59NU
51N
C70 CAPACITOR BANK RELAY
L5-7
87V
F4
L4
L1-3
spares
834758A1.CDR