RS485 serial interface
240
Festo – GDCP-CMMS/D-FW-EN – 1404NH – English
C
Serial interface RS485 (control interface)
C.1
Activating the motor controller via the interface RS485
C.1.1
Master data of the interface RS485
Parameter
Significance
Baud rate
9.6
1)
…115 KBit/s
Data bits
8
Parity
none
Stop bit
1
1)
Factory setting
Tab. C.1
Basic setting
For additional information
“Mounting and installation” description,
GDCP-CMMS-AS-G2-HW-…/GDCP-CMMD-AS-HW-…/GDCP-CMMS-ST-G2-HW-…
C.1.2
Connection [X5]: Pin allocation of the RS485 interface
Collision with interface “RS232”.
If the control interface “RS485” is activated, interface “RS232” remains active. If the pins
“2” and “3” in the cable are contacted on both plugs, this can result in the interfaces
“RS232” and “RS485” simultaneously accessing the motor controller.
–
For communication with the “control interface RS485”, use a cable that corresponds
to the pin allocation “control interface RS485”.
For additional information
“Mounting and installation” description,
GDCP-CMMS-AS-G2-HW-…/GDCP-CMMD-AS-HW-…/GDCP-CMMS-ST-G2-HW-…