Technical data
For more information visit:
www.EatonElectrical.com
MN05013005E
421
Making capacity, IEC 60947
AC-15 250 V AC, 3 A (600 Ops/h)
Switch
operations
300000
DC-13 L/R 150 ms 24 V DC, 1 A (500 Ops/h)
Switch
operations
200000
Breaking capacity, IEC 60947
AC-15 250 V AC, 3 A (600 Ops/h)
Switch
operations
300000
DC-13 L/R 150 ms 24 V DC, 1 A (500 Ops/h)
Switch
operations
200000
Filament lamp load
1000 W at 230/240 V AC
Switch
operations
25000
500 W at 115/120 V AC
Switch
operations
25000
Fluorescent tube with ballast, 10
×
58 W at 230/240 V AC
Switch
operations
25000
Conventional fluorescent tube, compensated,
1
×
58 W at 230/240 V AC
Switch
operations
25000
Conventional fluorescent tube, uncompensated,
10
×
58 W at 230/240 V AC
Switch
operations
25000
Operating frequency, relays
Mechanical switch operations
Switch
operations
10 mill. (10
7
)
Mechanical switching frequency
Hz
10
Resistive lamp load
Hz
2
Inductive load
Hz
0.5
EZD-R..