Function blocks
For more information visit:
www.EatonElectrical.com
MN05013005E
249
Parameter display and parameter set for the PUT function
block:
Input
The function block input
>I1
can be assigned the following
operands:
• Constants
• Markers MD, MW, MB
• Analog inputs IA01 to IA04
– IA01: terminal I7
– IA02: terminal I8
– IA03: terminal I11
– IA04: terminal I12
• Analog output QA01
• Actual value
…
QV> of another function block
Contacts
PT01Q1 to PT32Q1: state of the trigger coil
Coils
PT01T to PT32T: trigger coils
Memory requirement of the PUT function block
The PUT function block requires 36 bytes of memory plus
4 bytes per constant on the function block input.
PUT diagnostics
The PUT function block only functions when the EZ-NET
network is functioning correctly (
the individual stations and diagnostics”,
PT01 11
-
>I1
PT01
PUT function block (places a value onto the network),
number 11
-
Does not appear in the parameter display
>I1
Setpoint value which is put onto the EZ-NET network