Function blocks
For more information visit:
www.EatonElectrical.com
MN05013005E
187
Figure 100: EZD circuit diagram with counter relay
Parameter display and parameter set for the counter
relay:
In the parameter display of a counter relay you change
setpoint values and/or the preset value and the enabling of the
parameter display.
Value range
The function block operates in the integer range from
–2147483648 to 2147483647.
Behavior when value range is exceeded
The function block sets the switching contact C .. CY to the
status 1 and retains the value of the last valid operation.
I 05---------------------------Ä C 20C_
I 06---------------------------Ä C 20RE
I 07---------------------------Ä C 20D_
I 08---------------------------Ä C 20SE
C 20OF-------------------------Ä Q 01
C 20FB-------------------------Ä Q 02
C 20ZE-------------------------Ä Q 03
C 20CY-------------------------S M 42
C 20
+
>SH
>SL
>SV
QV>
C 20
Counter relay function block number 20
+
Appears in the parameter display
>SH
Upper setpoint
>SL
Lower setpoint
>SV
Defined actual value (Preset)
QV>
Actual value in RUN mode
J
The counter C counts every rising edge on the counter
input. If the value range is exceeded, the switching contact
C ..CY switches to status 1 for one cycle per rising edge
detected.