For more information visit:
www.EatonElectrical.com
Installation
MN05013005E
56
The following applies to expansion units:
With longer cables, connect a diode (e.g. 1N4007) for 1 A,
minimum 1 000 V reverse voltage, in series to the EZ input.
Ensure that the diode is pointing towards the input as shown
in the circuit diagram, otherwise EZ will not detect the 1 state.
Figure 36: EZ-AC with a diode on the inputs
Two-wire proximity switches have a residual current with the
“0” state. If this residual current is too high, the EZ input may
detect a “1” signal.
If inputs with a higher input current are required, an additional
input circuit must be used.
L1
N
R10
R9
R8
R7
R6
R5
R4
R3
R2
R1
E+ E–
R11 R12
N
N
L
115/230 V
h
F1