Technical data
For more information visit:
www.EatonElectrical.com
MN05013005E
423
Lamp load
Q1 to Q4 without
R
V
W
5
Residual current at state “0” per channel
mA
< 0.1
Max. output voltage
On 0 state with external load, 10 M
Ω
V
2.5
On 1 state,
I
e
= 0.5 A
U
=
U
e
– 1 V
Short-circuit protection
Thermal (Q1 to Q4)
(evaluation with diagnostics inputs I16, I15)
Yes
Short-circuit tripping current for
R
a
10 m
Ω
(depending on number of active channels and their load)
A
0.7
I
e
2
Maximum total short-circuit current
A
8
Peak short-circuit current
A
16
Thermal cutout
Yes
Maximum switching frequency with constant resistive load
R
L
= 100 k
Ω
(depends on program and load)
Switch
operations/
h
40000
Parallel connection of outputs with resistive load; inductive load with
external suppression circuit (
Section “Connecting transistor outputs”,
Page 67); combination within a group
Yes
Group 1: Q1 to Q4
Maximum number of outputs
4
Total maximum current
Attention!
Outputs must be actuated simultaneously and for the
same time duration.
A
2
Status display of the outputs
LCD Status display (if
provided)
EZD-T..