IB02602004E
For more information visit: www.eaton.com
Instructional Literature
Effective: May 2008
Page
7
Instructions for the FP-6000 Protective Relay
1.9 Function Matrix
All of the protective functions found in the FP-6000 are listed in the matrix below. Each entry includes the numbers for the pages in
the manual that provide additional information for that function.
Table 3. Function Matrix.
DEVICE NUMBER
PROTECTIVE FUNCTION
CONFIGURE IN:
PAGE REF.
25
Sync Check
Protection Sync Check Menu
69
27A-1
Auxiliary Vx Undervoltage
Protection Aux V Menu
66
27A-2
27M-1
Auxiliary Vx Undervoltage
Main Undervoltage
Protection Alarm Menu
Protection Main V Menu
70
66
32-1
32-2
Power Protection
Protection Power Protection Menu
67
32-3
Power Protection
Protection Alarms Menu
70
46-1
Current Unbalance
Protection Unbalance Menu
65
46-2
Current Unbalance
Protection Alarm Menu
70
47-1
Voltage Unbalance
Protection Unbalance Menu
65
47-2
Voltage Unbalance
Protection Alarm Menu
70
50BF
Breaker Failure
Protection Breaker Failure Menu
67
50P-1
50P-2
50P-3
Phase Instantaneous Overcurrent
with Directional Supervision (67)
50P-1 50P-2 in Protection Phase Overcurrent Menu
50P-3 in Protection Alarm Menu
63
63
70
50R-1
50R-2
50R-3
Residual Ground Instantaneous Overcurrent
with Directional Supervision (67)
50R-1, 50R-2 in Protection Phase Overcurrent Menu
50R-3 in Protection Alarm Menu
65
70
50X-1
50R-2
50R-3
Measured Ground Instantaneous Overcurrent
with Directional Supervision (67)
50X-1, 50X-2 in Protection IX Measured Overcurrent Menu
50X-3 in Protection Alarm Menu
64
70
51P
Phase Inverse-Time Overcurrent
with Directional Supervision (67)
Protection Phase Overcurrent Menu
63
51R
Residual Ground Inverse-Time Overcurrent
with Directional Supervision (67)
Protection IR Residual OC Menu
65
51V/51P2
Phase Inverse-Time Overcurrent with Directional
Supervision (67) & Voltage Restrained Overcurrent
Voltage Restraint in ProtectionPhase Overcurrent Menu
for 51P2
63
51X
Phase INverse-Time Overcurent with
Directional Supervision (67)
Protection IX Measured OC Menu
64
55A
Apparent Power Factor
Protection Power Factor Menu
68
55D
Displacement Power Factor
Protection Power Factor Menu
68
59A-1
Auxiliary Vx Overvoltage
Protection Aux V Menu
66
59A-2
Auxiliary Vx Overvoltage
Protection Alarm Menu
71
59M-1
Main Overvoltage
Protection Main V Menu
66
59M-2
Main Overvoltage
Protection Alarm Menu
70
59N-1
Neutral Overvoltage
Protection Neutral V Menu
66
59N-2
Neutral Overvoltage
Protection Alarm Menu
71
67P
Phase Directional Supervision of
50P-1, 50P-2, 50P-3, 51P, 51P2
Directional setpoints in System Configuration Menu
Configure 50P & 51P functions in Protection OC Menu
63
67G
(67pol,
67Q, 67V)
Ground Direction Supervision of
50R-1, 2, 3 & 50X-1, 2, 3, 51X, 51R
Directional Setpoints in System Configuration Menu
50 & 51X & R Functions in Protection OC Menu
63
64
65
810-1
810-2
Over Frequency
Over Frequency
Protection Frequency Menu
Protection Alarm Menu
67
71
81U-1
81U-2
Under Frequency
Under Frequency
Protection Frequency Menu
Protection Alarm Menu
67
71
Breaker Alarms
Systems Alarm Menu
77
Cold Load Pickup
Cold Load Pickup Menu
87
LOP
THD
Loss of Potential Used to Block Voltage Restraint
Power Protection Functions on Voltage Loss
Total Harmonic Distortion Alarms
Protection Main Menu
System Alarms Menu
66
76
Watt, VAR, VA Power Alarms
System Alarms Menu
76
Zone Interlocking
Protection Zone Interlocking Menu
68