Instructional Literature
Page
78
Effective: May 2008
Instructions for the FP-6000 Protective Relay
For more information visit: www.eaton.com
IB02602004E
Table 14. Logging Settings.
DISPLAY SETTING
DESCRIPTION
SETPOINT RANGE/
VALUE SELECTION
DEFAULT
SETTING
SELECTED
VALUE
REFER TO SEC. #
Current Demand
Current Demand Logging Setting
5.4.4
Interval (m):
Select interval for taking current demand mea-
surement in minutes
1 to 60 minutes
(Increments of 1)
15
Power Demand
Power Demand Logging Setting
5.4.4
Window:
Select type of power demand window
Fixed or Slide
Fixed
Interval (m):
Select interval for taking power demand mea-
surement in minutes
1 to 60 minutes
(Increments of 1)
15
Event Log Enable
Even Log Settings for Pickups, Contact Inputs
and Communications
5.4.4
12.2.1
I Pickup:
Select I Pickup to be logged
No, Yes
Yes
V Pickup:
Select V Pickup to be logged
No, Yes
No
Freq Pickup
Select Freq Pickup to be logged
No, Yes
No
PF Pickup:
Select PF Pickup to be logged
No, Yes
No
Unbal Pickup:
Select Unbal Pickup to be logged
No, Yes
No
SysAlm Pickup:
Select system alarm pickup to be logged
No, Yes
No
Power Pickup:
Select power pickup to be logged
No, Yes
No
Logic Pickup:
Select logic pickup to be logged
No, Yes
No
RTD Pickup:
Select thermal pickup to be logged
No, Yes
No
Var Pickup:
Select var pickup to be logged
No, Yes
No
Cin1:
Set Cin1 event to be logged
No, Yes
No
Cin2:
Set Cin2 event to be logged
No, Yes
No
Cin3:
Set Cin3 event to be logged
No, Yes
No
Cin4:
Set Cin4 event to be logged
No, Yes
No
Cin5:
Set Cin5 event to be logged
No, Yes
No
Cin6:
Set Cin6 event to be logged
No, Yes
No
Cin7:
Set Cin7 event to be logged
No, Yes
No
Cin8:
Set Cin8 event to be logged
No, Yes
No
Comm.:
Set Comm event to be logged
No, Yes
No
Datalogger
Datalogger Settings
5.4.4
Mode:
Select mode of datalogger to be continuous
(overwrites) or 1-pass
Cont. or 1-Pass
Cont.
8.11
Trigger:
Select trigger type
Auto or manual
Auto
Interval (s):
Select interval of datalogging in seconds
1 to 3600 seconds (increments of 1)
900
Value 1:
Set Value 1 to be logged
IA, IB, IC, IX, IR, Iavg, I0, I1, I2, VA, VB,
VC, VX, VLNavg, VAB, VBC, VCA
VLLavg, V0, V1, V2, Freq, W, VAR, VA,
Dsp PF, App PF, IA Demand, IB
Demand, IC Demand, W Demand, VAR
Demand, VA Demand, Cin1, Cin2, Cin3,
Cin4, Cin5, Cin6, Cin7, Cin8, LG1, LG2,
LG3, LG4, LG5, LG6, TG1, TG2, TG3,
TG4, TG5, TG6, IA THD, IB THD, IC
THD, VA THD, VB THD, VC THD, VAB
THD, VBC THD, VCA THD, RTD 1 to
RTD 11
Ia
Value 2:
Set Value 2 to be logged
Ib
Value 3:
Set Value 3 to be logged
Ic
Value 4:
Set Value 4 to be logged
Ix
Value 5:
Set Value 5 to be logged
Va
Value 6:
Set Value 6 to be logged
Vb
Value 7:
Set Value 7 to be logged
Vc
Value 8:
Set Value 8 to be logged
Vx