IB02602004E
For more information visit: www.eaton.com
Instructional Literature
Effective: May 2008
Page
79
Instructions for the FP-6000 Protective Relay
Note:
The I/O Configuration Setting in the System Configuration settings menu must be set to “custom” for these set points to be configured. Otherwise the default set-
tings displayed are used. See sections 5.4.5 and 5.4.6 for details.
Table 14. Logging Settings (continued).
DISPLAY SETTING
DESCRIPTION
SETPOINT RANGE/
VALUE SELECTION
DEFAULT
SETTING
SELECTED
VALUE
REFER TO SEC. #
Waveform Capture
Waveform Capture Settings
5.4.4
8.10
Records:
Select size of the waveform capture using
buffer x cycles
4x64, 8x32, 16x16 (buffer x cycles)
16x16
PreTrigger:
Select # of cycles of preTrigger data
1 to 15 cycles (increments of 1)
2
OSC Trigger TRIP1:
Select how to trigger waveform capture on
Trip 1 operation
Disable, Overwrite, or Lock
Lock
OSC Trigger TRIP2:
Select how to trigger waveform capture on
Trip 2 operation
Disable, Overwrite, or Lock
Overwrite
OSC Trigger dV/dI:
Select how to trigger waveform capture on a
V or I disturbance
Disable, Overwrite, or Lock
Disable
OSC Trigger Logic LG6:
Select how to trigger waveform capture on a
LG6 logic operation
Disable, Overwrite, or Lock
Overwrite
OSC Trigger Cntrl PB:
Select how to trigger waveform capture on
pushbutton operation
Disable, Overwrite, or Lock
Overwrite
OSC Trigger Comm:
Select how to trigger wave form capture on
communication command
Disable, Overwrite, or Lock
Overwrite
Table 15. Input Configuration Settings: Contact Input and RTD Configuration Settings
Input Configuration Settings.
DISPLAY SETTING
DESCRIPTION
SETPOINT RANGE/
VALUE SELECTION
DEFAULT
SETTING
SELECTED
VALUE
REFER TO SEC. #
Contact input CFG
Contact Input Configuration Settings
5.4.5
9.1
Cin1:
Select Cin1: configuration
user defined, 52a, 52b,
BFI, Bkr Trouble,
Remote Open,
Remote Close,
Remote Reset,
Datalog Trigger,
Demand Sync,
Sync Bypass,
Sync Block,
Select Set 1,
Select Set 2
52a
Cin2:
Select Cin2: configuration
52b
Cin3:
Select Cin3: configuration
BFI
Cin4:
Select Cin4: configuration
Bkr Trouble
Cin5:
Select Cin5: configuration
Remote Open
Cin6:
Select Cin6: configuration
Remote Close
Cin7:
Select Cin7: configuration
Remote Reset
Cin8:
Select Cin8: configuration
user defined
RTD Configuration Settings (RTD1 to RTD11.
DISPLAY SETTING
DESCRIPTION
SETPOINT RANGE/
VALUE SELECTION
DEFAULT
SETTING
SELECTED
VALUE
REFER TO SEC. #
Input Config (L1)
Input Configurations
52CSClosed, ARInit, ARBlock, IncShot,
ARLock, RstLock, Start1, Start2, Stop,
StartBlock, PD, ThermSwitch, Vibration,
Pressure, 87Trip, ZeroSpeed, TachPulse
RTD Input CFG (L2)
RTD Input Configurations
RTD1
RTD Channel 1
Ambient, Top Oil, Hot Spot, Ambient2, Top
Oil2, Hot Spot2 , Ambient3, Top Oil3, Hot
Spot3, Winding 1, Winding 2, Winding 3,
Winding 4, Winding 5, Winding 6,
Motor Bearing 1, Motor Bearing 2, Load
Bearing 1, Load Bearing 2,
User-defined, Off
Off
RTDx
RTD Channel x
See Above
Off
RTD11
RTD Channel 11
See Above
Off