Instructional Literature
Page
62
Effective: May 2008
Instructions for the FP-6000 Protective Relay
For more information visit: www.eaton.com
IB02602004E
1
This setting affects other settings. The user must save settings after changing this setting, which will take the user out of program mode. The user must then reenter
program mode to continue programming the remaining settings.
2
If enabled, the user must go to the “Test Mode” by pressing the “test button”, select Arm/Disarm Trip, then select Arm Trip or Disarm Trip setting.
3
CT secondary rating is automatically detected: I
nom
= 1 A or 5 A.
4
This setting is the programmed time delay for the T Delay setting of the time overcurrent Reset setting. See TOC Curve settings for 51P, 51R, and 51X elements.
Table 11. System Configuration (continued)
DISPLAY SETTING
DESCRIPTION
SETPOINT RANGE/
VALUE SELECTION
DEFAULT
SETTING
SELECTED
VALUE
REFER TO SEC. #
Cooling Tc
Cooling Time Constant
0.1 to 120 minutes
100 min
Tc @80%V
Maximum Cold Stall Time Tc @ 80%V
1 to 120 seconds
MaxStall Th
Maximum Hot Stall Time Th
1 to 120 seconds
Motor MVA
Motor Capacity MVA
Rated Volt
Motor Nameplate Voltage
100 to 20000 Volt
Rated pf
Rated Power Factor
0.01 to 0.99
Efficiency
Rated Motor Efficiency (n)
0.01 to 0.99
Rr0
Rotor Resistance @ Rated Motor Speed (R0)
0.01 to 10
MaxTemp Trl
Maximum Temperature Rise Trl
100 to 240
°
C (212 to 464
°
F)
240
NormTempTro
Normal Temperature Rise Tro
10 to 80
°
C, (50 to 176
°
F)
(Tro Can Be Estimated)
60
Ambient
Normal Ambient Temperature Ta
10 to 60
°
C (50 to 140
°
F)
40