IB02602004E
For more information visit: www.eaton.com
Instructional Literature
Effective: May 2008
Page
179
Instructions for the FP-6000 Protective Relay
Table 54. Logic Input Group Definitions.
Note:
All inputs can be negated from the front panel. An exclamation
mark, “!”, indicates the input is negated.
9.6.1 Example of Use
A simple example of the logic will illustrate the principles of
programming a logic diagram. This example shows how to add a
“High Load Alarm” function to the FP-6000.
•
Set the 50P-3 Phase IOC Alarm Pickup to 85% of the 51P TOC
Pickup setting. Go to “Set Mode” Protection ] Protection
Setting Group1 ] Alarms ] 50P-3 PH IOC Alarm ] Pickup and
enter a value of 0.85.
•
Use programmable logic to turn on the Programmable LED 8
and energize Output Relay 4.
•
Require the 50P-3 function pickup to be present for 1 second to
prevent spurious operation.
•
Maintain the output signal for 5 seconds after the current
drops below the pickup level.
•
Add an external switch to Contact Input 8 to enable or disable
the High Load Alarm at the user’s discretion.
A Timer Gate has an On Delay and/or an Off Delay that can be set
for up to 9999 cycles (166 minutes at 60 Hz). Use 60 cycles for an
On Delay of 1 second and 300 cycles for an Off Delay of 5
seconds. Figure 75 is an implementation of the “High Load
Alarm.”
The logic functions are programmed as follows from the main
settings menu:
•
Programmable Logic
@
Logic Gate1
@
Function:
AND
IN1:
Input CIn8
IN2:
Pickup 50P-3
•
Programmable Logic
@
Timer Gate1
@
In:
Logic LG1
On Delay (c):
60
Off Delay (c):
300
•
Output Config
@
Output Rly4
@
Function:
OR
IN1:
Logic TGI
•
LED Config
@
PLC LED8
@
Function:
OR
IN1:
Logic TGI
GROUP
INDIVIDUAL ELEMENTS
Ph OC
50P-1, 50P-2, 51P-1, 51P-2
Gnd OC
50X-1, 50X-2, 50R-1, 50R-2, 51X, 51R
IOC
50X-1, 50X-2, 50R-1, 50R-2, 50P-1,50P-2
TOC
51X, 51R, 51P-1, 51P-2
OC
50X-1, 50X-2, 50R-1, 50R-2, 50P-1,50P-2, 51X, 51R, 51P
All Alarm
50X-3, 50R-3, 50P-3, 59-A2, 27-A2,59-M2, 27-M2, 46-2, 47-2,
81U-2, 81O-2, LOPA, 32-3, 32V-3, 49DA, 49MA
Voltage
59-A1, 27-A1, 59-M1, 27-M1
Frequency
81U-1, 81O-1
All Protection
50X-1, 50X-2, 50R-1, 50R-2, 50P-1, 50P-2, 51X, 51R, 51P, 59-
A1, 27-A1, 59-M1, 27-M1, 46-1, 47-1, 81U-1 BF Pickup, Zone
Gnd, Zone Phase, 32-1, 32-2, 32V-1, 32V-2, 49DT, 49MT