Instructions for the FP-6000 Protective Relay
4.6.3.3 History Log
The History Log provides the Total History Log and the Breaker
History Log of FP-6000 trip events and breaker operations. This
information is useful for breaker maintenance. See Displays 15
and 16 for History Log displays.
Display 15. Total History Log.
Display 16. Breaker History Log
.
4.6.4 Status/Control
Press the “Status/Control”
pushbutton to view all of the FP-
6000 status and control
parameters. The red LED in the
upper left-hand portion of the
pushbutton area will illuminate
while you are in the Status/
Control Mode. Display 17 shows
the options displayed by
activating the “Status/Control”
pushbutton.
By using the
Up/Down
pushbutton and scrolling down through
the menu, the user can view additional information about the
status of all inputs, outputs and control logic of the FP-6000 relay
(see Display 17). By selecting the “Control” sub-menu, the user
can set the FP-6000 control parameters as shown in the
“Control” display. See Section 5 for programming the control
parameters. “Version” display gives the user access to view the
version of the product’s boot code and application code.
Total History Log
Display Meanings
Operate Hours:
00:00:00
Number of hours of operation.
# Power Up:
0
Number of times powered up.
# IOC Trips:
0
The number of instantaneous
overcurrent trips.
# TOC Trips:
0
The number of time
overcurrent trips.
# Unbal Trips:
0
The number of phase
unbalance trips.
# Volt Trips:
0
The number of voltage related
trips.
# Freq Trips:
0
The number of frequency trips.
# Power Trips:
0
The number of power trips.
# Total Trips:
0
The total number of trips.
# Bkr Ops:
0
The number of breaker
operations.
IA Accum:
0
Phase A accumulated
interrupted amperes.
IB Accum:
0
Phase B accumulated
interrupted amperes.
IC Accum:
0
Phase C accumulated
interrupted amperes.
RstTime:
00:00:00
The time of the last History Log
reset.
RstDate:
mm/dd/yy
The date of the last History Log
reset.
# Power Trips
Number of Power Trips
# Therm Trips
Number of Thermal Protection
Trips
# Var Trips
Number of Var Trips
# Total Trips
Total Number of Trips
Breaker History Log
Display Meanings
# Bkr Op:
0
The number of breaker operations.
IA Accum:
0
Phase A accumulated interrupted
amperes.
IB Accum:
0
Phase B accumulated interrupted
amperes.
IC Accum:
0
Phase C accumulated interrupted
amperes.
RstTime:
00:00:00
The time of the last Breaker Log
reset.
RstDate:
mm/dd/yy
The date of the last Breaker Log
reset.