Instructions for the FP-6000 Protective Relay
5.5 Default Settings
The Tables that follow show all of the System Configuration
settings and the remaining settings that are enabled, or turned
on, when the FP-6000 leaves the factory. If the user reverts back
to the default settings at any time when the unit is installed in the
field, the FP-6000 will revert back to the settings in this table.
Table 28. System Configuration.
SYSTEM CONFIG
SYSTEM CONFIG SETTINGS
DEFAULT SETTING
Frequency:
60
Phase Seq:
ABC
CT Connect:
3-wire
PH CT Ratio:
500:5
IX CT Ratio:
500:5
VT Connect:
Wye
VTRatio Exp
2
Main VTR:
100
Aux VTR:
100
VT Secondary Rating:
69.28
Prim Units:
No
I/O Config:
Default
Prog Logic:
Default
Remote Set:
Enable
Prg w/Bkr:
Either
Remote Bkr:
Disable
# Set Grps:
1
Set Ctrl:
Local
Disarm Ctrl:
Disable
Energy Unit:
kWh
TOC Reset T:
5
Bkr Oper PB:
Disable
Line Pos Seq Impedance Ang:
70
Line Zero Seq Impedance Ang:
70
IR Dir Cntrl:
Off
Gnd Dir V 3V0 Source:
Calculated
Gnd Dir V 3I0 Source
Calculated
IX Dir Cntrl:
Off
Ph Dir Switch to Mem
3
System Control (L2)
Temp Unit
°C
Motor Config (L2)
ThermI Type
RMS
Therm Model
User
I2 Multi K
6.0
FLA
500 A
LockRotor I
300%
MaxStall Tc
1 s
Service F
85%
Cooling Tc
100 min
MaxTemp Trl
150
NormTempTro
50
Ambient
20