IB02602004E
For more information visit: www.eaton.com
Instructional Literature
Effective: May 2008
Page
109
Instructions for the FP-6000 Protective Relay
Figure 26. Breaker Wear Curve.
Table 24. Breaker Curve: Select the Breaker Wear Curve Settings.
DISPLAY SETTING
DESCRIPTION
SETTING RANGE/
VALUE SELECTION
DEFAULT
SETTING
SELECTED
VALUE
REFER TO SEC. #
Breaker Curve (L1)
Breaker Custom Wear Curve Settings
5.4.12
Point 1 (L2)
Point 1 Settings
Cur 1 (pu)
Interrupted Current Level #1
0 to 40 pu
6
Count 1
Open Counts Allowed #1
1 to 0xFFFF
40
Point 2 (L2)
Point 2 Settings
Cur 2 (pu)
Interrupted Current Level #2
0 to 40 pu
12
Count 2
Open Counts Allowed #2
1 to 0xFFFF
30
Point 3 (L2)
Point 3 Settings
Cur 3 (pu)
Interrupted Current Level #3
0 to 40 pu
18
Count 3
Open Counts Allowed #3
1 to 0xFFFF
20
Point 4 (L2)
Point 4 Settings
Cur 4 (pu)
Interrupted Current Level #4
0 to 40 pu
24
Count 4
Open Counts Allowed #4
1 to 0xFFFF
15
Point 5 (L2)
Point 5 Settings
Cur 5 (pu)
Interrupted Current Level #5
0 to 40 pu
30
Count 5
Open Counts Allowed #5
1 to 0xFFFF
5
Point 6 (L2)
Point 6 Settings
Cur 6 (pu)
Interrupted Current Level #6
0 to 40 pu
36
Count 6
Open Counts Allowed #6
1 to 0xFFFF
1
Point 7 (L2)
Point 7 Settings
Cur 7 (pu)
Interrupted Current Level #7
0 to 40 pu
40
Count 7
Open Counts Allowed #7
1 to 0xFFFF
0
Point 8 (L2)
Point 8 Settings
Cur 8 (pu)
Interrupted Current Level #8
0 to 40 pu
40
Count 8
Open Counts Allowed #8
1 to 0xFFFF
0
Point 9 (L2)
Point 9 Settings
Cur 9 (pu)
Interrupted Current Level #9
0 to 40 pu
40
Count 9
Open Counts Allowed #9
1 to 0xFFFF
0
Point 10 (L2)
Point 10 Settings
Cur 10 (pu)
Interrupted Current Level #10
0 to 40 pu
40
Count 10
Open Counts Allowed #10
1 to 0xFFFF
0