IB02602004E
For more information visit: www.eaton.com
Instructional Literature
Effective: May 2008
Page
81
Instructions for the FP-6000 Protective Relay
1
This setting is only sued if the “Dropout” setting is set to “Off Delay
”
Table 16. Output Configuration Settings (continued).
DISPLAY SETTING
DESCRIPTION
SETPOINT RANGE/
VALUE SELECTION
DEFAULT
SETTING
SELECTED
VALUE
REFER TO SEC. #
Output Alarm Rly6
Output Alarm Relay 6 Settings
5.4.6
9.2
9.6
Function:
Select logic output function for Output Alarm
Rly6
OR, AND, NOR, NAND, disable
OR
Dropout:
Select relay state after trip occurs
Latched, unlatched, off delay
Unlatched
Off Delay (c):
Select delay for Relay to dropout after trip event
clears
1
0 to 600 cycles
(1 cycle increments)
0
IN1:
Select logic input IN1 for Output Rly6
*See Logic Input Options Table 18
Trip, All Prot
IN2:
Select logic input IN2 for Output Rly6
*See Logic Input Options Table 18
Trip, All Alm
IN3:
Select logic input IN3 for Output Rly6
*See Logic Input Options Table 18
Sys Alm, All
Alarm
IN4:
Select logic input IN4 for Output Rly6
*See Logic Input Options Table 18
Breaker, All Alm