IB02602004E
For more information visit: www.eaton.com
Instructional Literature
Effective: May 2008
Page
197
Instructions for the FP-6000 Protective Relay
Whenever the communication variable input changes, if so
programmed, it will be logged in the event log.
Table 66 shows the cause for this event log.
Table 66. Event Communication Cause Table.
As described in Section 12.1, the FP-6000 does a series of self
diagnostic checking. If any self test should fail, the event is
logged automatically in the event log. See Table 67 for a
complete list of self test event causes.
Table 67. Self Test Event Cause Table.
12.2.1.1 Active Alarm
Unlike the Event Log that contains a chronological list of events
that the FP-6000 has observed, the Active Alarm screen shows
the user what trips or alarms have occurred when they are
occurring. The Active Alarm screen will only show the events
that occur for the items you have programmed within the Alarm
Relay Output setting. The Alarm Relay Output default settings
are set to show any protection trips, any alarm trips, any system
trips and any breaker alarms. See section 9.1 and 9.5 for
additional information.
The events will remain on the Active Alarm screen until they
have been cleared either externally or through the FP-6000 unit.
The type of event that occurs dictates the procedures necessary
to clear the Active Alarm.
When the FP-6000 Active Alarm setting is “Unlatched” the Alarm
LED will turn itself off once all the events are cleared. However, if
the FP-6000 Active Alarm setting is “Latched” the Alarm LED will
remain on even after all the events has been cleared externally
or through the unit.
To clear the Latched Alarm after an event has been cleared, press
the Reset button. Scroll to Alarm and press the Enter pushbutton
two times. Once these steps are followed the Alarm LED will
turn off.
To prevent the Alarm LED from appearing after the event has
been cleared the FP-6000 Active Alarm setting must be set to
“Unlatched”. To do this simply press Set, enter the password,
scroll to Output Config and press Enter. Scroll to Alarm
Indicator, press Enter, scroll to Dropout and select Unlatched,
press Enter.
The following tables (68 and 69) show the types of events that
can appear on the Active Alarm screen and the steps needed to
clear that specific event for the default trips and alarms set within
the Alarm Relay Output.
If you require additional information contact the Power
Management Application Support team at 1-800-809-2772
option 1 / option 1.
CAUSE
CAUSE DESCRIPTION
VALUE GIVEN
CommLogic Alt
Communication Logic variable has changed state.
Communication Logic Status – contains all 4 communication logic variable states.
CAUSE
CAUSE DESCRIPTION
VALUE GIVEN
Bt Flash Err
Boot Flash Checksum Failure.
No value associated with this cause.
ProgFlash Err
Program Flash Checksum Failure.
No value associated with this cause.
Ext RAM Fail
External RAM Error.
Bad RAM Address.
TPU RAM Fail
Internal TPU RAM Error.
Bad Internal TPU RAM Address.
Analog In Err
Analog to digital conversion error.
No value associated with this cause.
Set Warning error has occurred
A recoverable Settings (setpoint).
No value associated with this cause.
Set Failure error has occurred
A nonrecoverable Settings (setpoint) .
No value associated with this cause.
Display Warn
Display Warning – read back test failed.
No value associated with this cause.
RelNotCalibra
No Calibration constants are present.
No value associated with this cause.
RAM Batt Warn
The nonvolatile RAM Battery is low.
No value associated with this cause.
Clock Warning
The real time clock has failed.
No value associated with this cause.
Test Mode
The Test Mode has been entered or exited.
Enter or Exit.
EEPROM Warning
The EEPROM has failed.
No value associated with this cause.
CalibrateWarn
A recoverable Calibration error has occurred.
No value associated with this cause.
CalibrateFail
A nonrecoverable Calibration error has occurred.
No value associated with this cause.