Instructional Literature
Page
74
Effective: May 2008
Instructions for the FP-6000 Protective Relay
For more information visit: www.eaton.com
IB02602004E
Table 12. Protection (continued).
Alarms Thermal:
Select Thermal Alarms Settings (RTD1 to RTD11 & 49M)
DISPLAY SETTING
DESCRIPTION
SETTING RANGE/
VALUE SELECTION
DEFAULT
SETTING
SELECTED
VALUE
REFER TO SEC. #
Protection/Setting
Group X (L1)
Protection Setting Menu
Thermal Alarm (L2)
Thermal Alarm Setting Menu
RTD1-1 Pickup
Alarm (L3)
RTD1-1 Pickup Alarm Settings
Pickup
RTD 1 Alarm 1 Pickup
Disable, 0 to 199
°
C, or 0 to 390
°
F
Disable
Delay (min)
RTD 1 Alarm 1 Pickup Delay
1 to 3600 min
10 min
RTD1-1 Dropout
Alarm (L3)
RTD1-1 Dropout Alarm Settings
Threshold
RTD 1 Alarm 1 Dropout
0 to 199
°
C, or
0 to 390
°
F
Disable
Delay (min)
RTD 1 Alarm 1 Dropout Delay
1 to 3600 min
10 min
RTD1-2 Pickup
Alarm (L3)
RTD1-2 Pickup Alarm Settings
Pickup
RTD 1 Alarm 2 Pickup
Disable, 0 to 19
9
°
C, or 0 to 390
°
F
Disable
Delay (min)
RTD 1 Alarm 2 Pickup Delay
1 to 3600 min
10 min
RTD1-2 Dropout
Alarm (L3)
RTD1-2 Dropout Alarm Settings
Threshold
RTD 1 Alarm 2 Dropout
0 to 199
°
C, or
0 to 390
°
F
Disable
Delay (min)
RTD 1 Alarm 2 Dropout Delay
1 to 3600 min
10 min
RTD2-1 Pickup
Alarm (L3)
RTD2-1 Pickup Alarm Settings
Pickup
RTD 2 Alarm 1 Pickup
Disable, 0 to 199
°
C, or 0 to 390
°
F
Disable
Delay (min)
RTD 2 Alarm 1 Pickup Delay
1 to 3600 min
10 min
RTD2-1 Dropout
Alarm (L3)
RTD2-1 Dropout Alarm Settings
Threshold
RTD 2 Alarm 1 Dropout
0 to 199
°
C, or
0 to 390
°
F
Disable
Delay (min)
RTD 2 Alarm 1 Dropout Delay
1 to 3600 min
10 min
RTD2-2 Pickup
Alarm (L3)
RTD2-2 Pickup Alarm Settings
Pickup
RTD 2 Alarm 2 Pickup
Disable, 0 to 199
°
C, or 0 to 390
°
F
Disable
Delay (min)
RTD 2 Alarm 2 Pickup Delay
1 to 3600 min
10 min
RTD2-2 Dropout
Alarm (L3)
RTD2-2 Dropout Alarm Settings
Threshold
RTD 2 Alarm 2 Dropout
0 to 199
°
C, or
0 to 390
°
F
Disable