background image

( date / name ): 25.03.08 shu/Fz 

Z. Nr.: 1120 0753.6

Page  1  of 16 

Type: TR 600 RS485 

ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: [email protected] 

Operating manual 

Pt 100 thermostat TR 600 with interface RS 485 

MINIPAN

®

 digital panel meters, temperature- and mains controlling,

special purpose instruments for customer requirements    

www.ziehl.com

 

- Archive document - 

www.ziehl.de

Summary of Contents for TR600

Page 1: ... KG Daimlerstr 13 D 74523 Schwäbisch Hall Tel 49 791 504 0 Fax 56 e mail info ziehl de Operating manual Pt 100 thermostat TR 600 with interface RS 485 MINIPAN digital panel meters temperature and mains controlling special purpose instruments for customer requirements www ziehl com Archive document www ziehl de ...

Page 2: ...x 56 e mail info ziehl de Contents Page Application and short description 3 Overview of functions 3 Connection plan 3 Display and operating elements 4 Function diagram 4 Important notes 5 Assembly 6 Putting into operation 6 Remarks 6 Table of function 8 Setup 8 Trouble shooting 9 Technical data 10 Form 12 Appendix 13 Data structure for serial transmission 13 Example 14 ...

Page 3: ...ramming is very variable and simple Due to the fact that 6 type Pt 100 sensors can be connected the unit is especially suitable for temperature monitoring wherever up to 6 different measuring points must be monitored simultaneously motors and generators with simultaneous monitoring of bearings and coolant transformers with additional monitoring of the core temperature also power machines and plant...

Page 4: ...G Daimlerstr 13 D 74523 Schwäbisch Hall Tel 49 791 504 0 Fax 56 e mail info ziehl de Display and operating elements 1 LED Sensor Error 2 6 x LED Sensor 3 6 x LED Alarm 4 Select buttons 5 Display 3 digits 6 Up button 7 Down button 8 Mode button 9 Set button 10 Display 1 digit Mode 11 Reset button Function diagram ...

Page 5: ...on f in any case the information in the instructions manual is not sufficient please contact our company or the responsible representative Instead of the industrial norms and regulations written in this instructions manual valid for Europe you must observe out of their geographical scope the valid and relevant regulations of the corresponding country Observe the maximum temperature permissible whe...

Page 6: ... point on temperature beyond switching point blinking 1x on 4x off alarm relay delay time tALARM is running blinking 4x on 1x off alarm relay delay time tALARM off is running blinking 1x on 1x off relay locked ready for reset Alarm relay can be reseted with reset push button or external contact closed Y1 Y2 A closed contact or short circuit at terminals Y1 Y2 means no auto reset function Operating...

Page 7: ... the sensor and measure the line resistance Setting see mode 6 We recommend to use 2 or better 3 wires for each sensor With 2 wire connection and a common line for all signals all sensor measuring currents will be added on the common line Thus the value of the compensation line resistance RK must be calculated as follows RK n 1 x RL 2 RL line resistance of two wires n number of sensors Sensor simu...

Page 8: ... 0 Switching Point C Relay 1 6 Sensor 1 6 199 800 C Store 100 C group 1 2 3 Alarm 1 Sensor 1 group 4 5 group 4 5 6 group 1 6 Alarm 6 Sensor 6 1 Hysteresis K Relay 1 6 1 20 K Store 3 K 2 tALARM s Relay 1 6 0 1 20 0 s Store 0 1 s 3 tALARM off s Relay 1 6 0 999 s Store 0 s 4 auto reset locked Relay 1 6 0 auto reset Store 0 auto reset 1 locked 5 Operating function Relay 1 6 Max NO contact Sensor alarm...

Page 9: ...r See setup mode 9 Failure display E 0 sensor error relay K7 switching Operation failure Switch off the supply voltage and restart When the failure is still going on the relay should be replaced and send to the factory Failure display E 1 or E 2 sensor error relay K7 switching EEPROM parameter failure Check all programmed parameters and setup new when necessary Switch off the supply voltage and re...

Page 10: ...erational current Ie AC15 Ie 1 A Ue 400 V Ie 2 A Ue 250 V DC13 Ie 2 A Ue 24 V Ie 0 2 A Ue 125 V Ie 0 1 A Ue 250 V Recommended fuse for contacts T 3 15 A gL Expected life mechanical 1 x 107 operations Expected life electrical 1 x 105 operations with AC 250 V 5 A 2 x 105 operations with AC 250 V 3 A 6 x 105 operations with AC 250 V 1 A Test conditions EN 60947 EN 50178 Insulation EN 60664 Rated impu...

Page 11: ...9200 Baud Max Ambient Temperature Operating Temperature 20 C 65 C Storage Temperature 20 C 70 C no condensation permitted Housing Type V8 Dimensions H x W x D 140 x 90 x 58 mm Mounting height Width 55 mm 4 TE Line connection solid wire 1 x 1 5 mm2 Stranded wire with insulated ferrules 1 x 1 0 mm2 Torque 0 5 Nm 3 6 lb in Protection class housing IP 31 Protection class terminals IP 20 Fitting positi...

Page 12: ...il info ziehl de 48 58 45 3 61 8 16 5 Option 98 105 140 116 90 1 2 3 4 5 6 7 Form V8 dimensions in mm 1 Oberteil cover 2 Unterteil base 3 Riegel bar for snap mounting 4 Plombenlasche latch for sealing 5 Frontplatteneinsatz front panel 6 Kennzeichen für unten position downward 7 Riegel bei Wandbefestigung mit Schrauben Riegelbohrung Ø 4 2 mm for fixing to wall with screws Ø 4 2 mm ...

Page 13: ...S ASCII STX 0x2 1 Byte Data Type of unit TR600 ASCII 5 Byte separated by Address of unit 00 99 ASCII 2 Byte separated by Mode of data 0 9 ASCII 1 Byte separated by Temperature sensor 1 199 800 ASCII 1 4 Byte separated by Temperature sensor 2 199 800 ASCII 1 4 Byte separated by Temperature sensor 3 199 800 ASCII 1 4 Byte separated by Temperature sensor 4 199 800 ASCII 1 4 Byte separated by Temperat...

Page 14: ...Block check exor of all transmitted bytes Data Mode 0 Mode 0 Read command r read Address of unit 01 99 ASCII Start of message s S or STX Block sum s 115 exor 0 48 exor 1 49 exor r 114 exor 0 48 048 The values in brackets correspond with the ASCII code of the sign TR 600 answers sTR600 01 0 154 055 268 999 980 999 1 0 0 1 0 0 1 02 119 r n Data mode Address of unit Type of unit Start of message Temp...

Page 15: ...e 15 of 16 Type TR 600 RS485 ZIEHL industrie elektronik GmbH Co KG Daimlerstr 13 D 74523 Schwäbisch Hall Tel 49 791 504 0 Fax 56 e mail info ziehl de You ll find this and other user manuals also in English written in the internet under www ziehl com ...

Page 16: ...e 16 of 16 Type TR 600 RS485 ZIEHL industrie elektronik GmbH Co KG Daimlerstr 13 D 74523 Schwäbisch Hall Tel 49 791 504 0 Fax 56 e mail info ziehl de You ll find this and other user manuals also in English written in the internet under www ziehl com ...

Reviews: