Instructions for the FP-6000 Protective Relay
4.3 Pushbuttons
The front operations panel supports 15 membrane switch
pushbuttons. Pressing any of the pushbuttons will initiate many
of the FP-6000 functions and actions. This section gives a
complete description of each pushbutton and its functions. The
pushbuttons can be grouped logically into the 6 display modes,
reset, and breaker control.
1. Reset
5. Status/Control
2. Monitor
6. Set (Settings)
3. View Setting
7. Test
4. Log
8. Close Open Breaker
The center section consists of display navigation buttons:
1. Previous
2. Up/Down (single arrow)
3. Enter
“
Reset” Pushbutton:
The “Reset” pushbutton performs
many “Reset” functions, one of
which resets the display to show
the default rms current and
voltage display screen from any
display menu, when the relay is in
normal monitoring mode.
The FP-6000 has a “Reset” menu,
which is accessed by pressing the
“Reset” pushbutton when the
unit is in normal monitoring
mode. This menu allows the user
to reset all of the relay functions:
trips, alarms, peak current and
power demands, min/max values,
history log parameters, relays
and the data logger. There is no
password protection for the reset
functions. (See Display 2)
Display 2. Reset.
The user can reset a function by selecting a reset sub-menu
function, listed above. Simply use the
Up/Down
arrow to move
the screen’s arrow to the function you want to reset and push the
Enter
pushbutton. Below is an example of the sub-menu reset
display screen when the “Trip” function is selected.
Reset Main
Trip
Alarm
Bkr Lockout
AR Lockout
Slow Bkr ALM
Relay
Peak Demand Values
Min/Max Values
History Log
Datalog
Energy
Display
Diag Warnings
Reset Logic Latches
Clear Wave Form Lock
Reset Trip
Press
ENTER To Confirm
PREVIOUS To Cancel