IB02602004E
For more information visit: www.eaton.com
Instructional Literature
Effective: May 2008
Page
21
Instructions for the FP-6000 Protective Relay
Table 5. Table of Specifications (continued).
PROTECTIVE FUNCTION PICKUP ACCURACY
TRIP ACCURACY — PICKUP AND TRIP TIME RELATIVE TO PROGRAMMED:
Trip
Trip Description
Pickup
Trip Time Accuracy
Accuracy
50X-1
Ground Trip (IX IOC)
±0.5%
2
0 to + 2 Cycles or 0.1%, Whichever Is Greater
50X-2
Ground Trip (IX IOC)
±0.5%
2
0 to + 2 Cycles or 0.1%, Whichever Is Greater
50R-1
Ground Trip Residual
(IR IOC)
±3%
3
0 to + 2 Cycles or 0.1%, Whichever Is Greater
50R-2
Ground Trip Residual
(IR IOC)
±3%
3
0 to + 2 Cycles or 0.1%, Whichever Is Greater
50P-1
Phase Trip (Ph IOC)
±0.5%
2
0 to + 2 Cycles or 0.1%, Whichever Is Greater
50P-2
Phase Trip (Ph IOC)
±0.5%
2
0 to + 2 Cycles or 0.1%, Whichever Is Greater
55A
Apparent PF Trip
±0.02
0 to + 0-1.2 Sec.
55D
Apparent PF Reset
±0.02
0 to + 0-1.2 Sec.
59M-1
Voltage Main Over
±0.5%
4
0 to + 2 Cycles or 0.1%, Whichever Is Greater
59N-1
Neutral Overvoltgage
±0.5%
4
0 to + 2 Cycles or 0.1%, Whichever Is Greater
27M-1
Voltage Main Under
±0.5%
4
0 to + 2 Cycles or 0.1%, Whichever Is Greater
32-1
Power
±1%
0 to + 2 Cycles or 0.1%, Whichever Is Greater
32-2
Power
±1%
0 to + 2 Cycles or 0.1%, Whichever Is Greater
59A-1
Voltage Aux. Over
±0.5%
4
0 to + 2 Cycles or 0.1%, Whichever Is Greater
27A-1
Voltage Aux. Under
±0.5%
4
0 to + 2 Cycles or 0.1%, Whichever Is Greater
81O-1
Over Frequency
±0.02 Hz
0 to + 6 Cycles or 0.1%, Whichever Is Greater
81U-1
Under Frequency
±0.02 Hz
0 to + 6 Cycles or 0.1%, Whichever Is Greater
47-1
Voltage Unbalance
±1%
4
0 to + 2 Cycles or 0.1%, Whichever Is Greater
47-2A
Voltage Unbalance
±1%
4
0 to + 2 Cycles or 0.1%, Whichever Is Greater
46-1
Current Unbalance
±1%
2
0 to + 2 Cycles or 0.1%, Whichever Is Greater
46-2A
Current Unbalance
±1%
2
0 to + 2 Cycles or 0.1%, Whichever Is Greater
32V-1, 32V-2
Var trip
±1%
0 to + 2 Cycles or 0.1%, Whichever is greater
32V-3
Var alarm
±1%
0 to + 2 Cycles or 0.1%, Whichever is greater
49DT
RTD trip
1 C
0 to + 2 Cycles or 0.1%
49DA
RTD alarm
1 C
0 to + 2 Cycles or 0.1%
49MT
Thermal replica model trip
49MA
Thermal replica model alarm
TIME OVERCURRENT
51P
Phase Trip (Ph TOC)
0.5%
2
+3% or + 2 Cycles, Whichever Is Greater
5
51P2
Phase Trip (Ph TOC)
0.5%
2
+3% or + 2 Cycles, Whichever Is Greater
5
51R
Ground Trip Residual
(IR TOC)
3%
3
+3% or + 2 Cycle Whichever Is Greater
5
51X
Ground Trip (IX TOC)
0.5%k
+3% or + 2 Cycles, Whichever Is Greater