Table 27. AR Settings: Select the AR Settings (continued).
DISPLAY SETTING
DESCRIPTION
SETTING RANGE /
VALUE SELECTION
DEFAULT
SETTING
SELECTED
VALUE
REFER TO SEC. #
AR Block I Unbal (L4)
Autoreclose Block Unbalance Current Functions
46-1 Trip
Shot 4 Block 46-1
Yes, No, Accelerate (0 to 60c)
Yes
46-2 Trip
Shot 4 Block 46-2
Yes, No, Accelerate (0 to 60c)
Yes
Ground TOC Pickup (L4)
Ground Time Inverse Overcurrent Pickup Settings
51X Pickup
Shot 4 51X Pickup
0.1 to 4 pu, Disable
1.00 pu
51R Pickup
Shot 4 51R Pickup
0.1 to 4 pu, Disable
1.00 pu
51Q Pickup
Shot 4 51Q Pickup
0.1 to 4 pu , Disable
1.00 pu
Phase TOC Pickup (L4)
Phase Time Inverse Overcurrent Pickup Settings
51P Pickup
Shot 4 51P Pickup
0.1 to 4 pu , Disable
2.00 pu
51P2 Pickup
Shot 4 51P2 Pickup
0.1 to 4 pu , Disable
Disable
AR Block Power 32W (L4)
Autoreclose Block Power Functions
32W Trip
Shot 4 Block 32W Trip
Yes, No
Yes
32W Alarm
Shot 4 Block 32W Alarm
Yes, No
Yes
AR Block 50Q (L4)
Autoreclose Block Negative Sequence Overcur-
rent Functions
50Q-1 Trip
Shot 4 Block 50Q-1
Yes, No, Accelerate (0 to 60c)
Yes
50Q-2 Trip
Shot 4 Block 50Q-2
Yes, No, Accelerate (0 to 60c)
Yes
50Q-3 Trip
Shot 4 Block 50Q-3
Yes, No, Accelerate (0 to 60c)
Yes
AR Block Var 32V (L4)
Autoreclose Block Var Functions
32V Trip
Shot 4 Block 32V Trip
Yes, No
Yes
32V Alarm
Shot 4 Block 32V Alarm
Yes, No
Yes