122
DPMS XPQ User Manual
Sequence Component
U1 (U12), I1 consist of real and complex parts. They have positive
sequence, negative sequence and zero sequence. Data type is “int”.
Function code: 03H for Reading.
Address
Parameter
Range
Format code
44a8H
positive sequence real part of UA
-32768~32767
F7
44a9H
positive sequence complex part of UA
-32768~32767
F7
44aaH
negative sequence real part of UA
-32768~32767
F7
44abH
negative sequence complex part of UA -32768~32767
F7
44acH
zero sequence real part of UA
-32768~32767
F7
44adH
zero sequence complex part of UA
-32768~32767
F7
44aeH
positive sequence real part of IA
-32768~32767
F8
44afH
positive sequence complex part of IA
-32768~32767
F8
44b0H
negative sequence real part of IA
-32768~32767
F8
44b1H
negative sequence complex part of IA
-32768~32767
F8
44b2H
zero sequence real part of IA
-32768~32767
F8
44b3H
zero sequence complex part of IA
-32768~32767
F8
Phase Angle
All voltage and current’s phase angles corresponding to V1 (V12) are
stored here. You can find out the phase sequence according to them. Data type
is “word”.
Function code: 03H for Reading.
Address Parameter
Range
Format code
44b4H
phase angle of V2 to V1
0~3600
F22
44b5H
phase angle of V3 to V1
0~3600
F22
44b6H
phase angle of V2 to V1
0~3600
F22
44b7H
phase angle of I2 to V1
0~3600
F22
Summary of Contents for XPQ
Page 1: ...POWER INSTRUMENTS DPMS XPQ Multi Function Power Meter User Manual 1087 332...
Page 2: ......
Page 7: ...Chapter 1 Introduction Purpose Application Area Functions DPMS XPQ Series 5...
Page 13: ...Chapter 2 Installation Appearance and Dimensions Installation Method Wiring 11...
Page 30: ...28 DPMS XPQ User Manual 6 2LL 2CT Fig 2 23 2LL 2CT 7 2LL 1CT Fig 2 24 2LL 1CT...
Page 59: ...Chapter 4 Function and Software Functionality and Utility Software 57...
Page 68: ...66 DPMS XPQ User Manual Here is an example Fig 4 7 Demand Here is to set demand...
Page 90: ...88 DPMS XPQ User Manual Fig 4 20 Voltage Eligibility Ratio...
Page 126: ...124 DPMS XPQ User Manual...
Page 127: ...125 Appendix Appendix A Technical Data and Specifications Appendix B Ordering Information...
Page 133: ......