34
DPMS XPQ User Manual
overall length of the RS485 cable connecting all devices can not exceed 1200m
(4000ft). The DPMS XPQ is used as a slave device of a master like a PC, PLC,
data collector or RTU.
If the master does not have an RS485 communication port, a converter has
to be used. Normally a RS232/RS485 or USB/RS485 is adopted. The topology
of RS485 net can be line, circle and star.
1. Line
The connection from master to meter is one by one in the RS485 net as in
fig 2.32.
fig 2.31 Line Mode
In fig 2.32 the Rt is an anti-signal reflecting resistor 120-300 ohm/0.25W.
Normally, it is added to the end of the circuit beside the last meter, if the
communication quality is not good.
2. Circle
Meters are connected in a closed circle for the purpose of high reliability.
There is no need for anti-signal reflecting resistors.
Fig 2.32 Line mode
Converter
Acuvim-X
Acuvim-X
Acuvim -X
Master
PC
Summary of Contents for XPQ
Page 1: ...POWER INSTRUMENTS DPMS XPQ Multi Function Power Meter User Manual 1087 332...
Page 2: ......
Page 7: ...Chapter 1 Introduction Purpose Application Area Functions DPMS XPQ Series 5...
Page 13: ...Chapter 2 Installation Appearance and Dimensions Installation Method Wiring 11...
Page 30: ...28 DPMS XPQ User Manual 6 2LL 2CT Fig 2 23 2LL 2CT 7 2LL 1CT Fig 2 24 2LL 1CT...
Page 59: ...Chapter 4 Function and Software Functionality and Utility Software 57...
Page 68: ...66 DPMS XPQ User Manual Here is an example Fig 4 7 Demand Here is to set demand...
Page 90: ...88 DPMS XPQ User Manual Fig 4 20 Voltage Eligibility Ratio...
Page 126: ...124 DPMS XPQ User Manual...
Page 127: ...125 Appendix Appendix A Technical Data and Specifications Appendix B Ordering Information...
Page 133: ......