126
DPMS XPQ User Manual
Appendix A Technical data and specifications
Input Ratings
Voltage Input
Voltage rating 40~230VAC LN, 60~400VAC L-L
with 20% over range
Category III, Pollution degree 2
Frequency range 45~65Hz
Overload 2 times for continue,
2500Vac for 1 Sec (None recurrence)
Voltage range through PT 500KV highest at primary side
PT burden <0.2VA
Measuring True RMS
Current Input
Current rating 5Amp AC nominal F.S. input
with 20% over range.
1Amp (Optional)
Current range 50000A highest at primary side
Overload 10A for continuous
100A for 1 Sec(None recurrence)
CT burden < 0.5VA
Measuring True RMS