POWER INSTRUMENTS
2. Global settings
The addresses of all global variables are 101dH~1024H and 103dH in
system parameters discussed in chapter 5. “Alarming enable” determines
whether the alarming function of this meter works. Only when it is set as “1”,
the alarming function enables. When “Alarming flash enable“ is set to “1”, the
backlight will flash when an alarm happens.
“Alarming records enable setting” determines whether it records. There are
16 records in all and each one corresponds to one bit of a 16-bit register. For
each record, it works or not depending on the enable setting. If some bits of the
register are “1”, it means their corresponding records take effect.
“Relay for alarming setting”: There are two relays. They can be used as
remote controlling output and alarming output. But one can’t work in two modes
at the same time. “1” means the relay works in alarming mode and “0” for
remote controlling mode. This setting is valid for both relays.
“Alarming output to RO1 setting”: when “Relay for alarming setting” is set
to be “1”, the relay is available for alarming, but which record it will be driven by
and whether output to RO1 or RO2 will depend on other settings. This setting
will give an answer. There are 16 records in all and each one corresponds to
one bit of a 16-bit register, when the corresponding bit is set to “1”, the relay
will close if the alarming condition is satisfied. It opens only when all the alarms
related to RO1 recover. If the corresponding bit is set to “0”, RO1 will not be
disturbed.
Note:
When the relay is used in alarming mode, it works in latching mode. There
is no pulse mode. So all setting of the relay's working mode will be ignored.
Summary of Contents for XPQ
Page 1: ...POWER INSTRUMENTS DPMS XPQ Multi Function Power Meter User Manual 1087 332...
Page 2: ......
Page 7: ...Chapter 1 Introduction Purpose Application Area Functions DPMS XPQ Series 5...
Page 13: ...Chapter 2 Installation Appearance and Dimensions Installation Method Wiring 11...
Page 30: ...28 DPMS XPQ User Manual 6 2LL 2CT Fig 2 23 2LL 2CT 7 2LL 1CT Fig 2 24 2LL 1CT...
Page 59: ...Chapter 4 Function and Software Functionality and Utility Software 57...
Page 68: ...66 DPMS XPQ User Manual Here is an example Fig 4 7 Demand Here is to set demand...
Page 90: ...88 DPMS XPQ User Manual Fig 4 20 Voltage Eligibility Ratio...
Page 126: ...124 DPMS XPQ User Manual...
Page 127: ...125 Appendix Appendix A Technical Data and Specifications Appendix B Ordering Information...
Page 133: ......