32
DPMS XPQ User Manual
There are two mode selections for relay output, one is latching, and the
other is momentary. For the latching mode, the relay can be used to output two
states, on or off. For the momentary mode, the output of the relay changes from
off to on for a period of time Ton and then goes off. Ton can be set from 50-
3000ms.
The wire for relay output should be between AWG22 (0.5mm
2
)~AWG16
(1.3mm
2
).
Digital Output (DO)
There are two digital outputs as an option. The terminals of the digital
output are DO1+, DO1-(35, 36) and DO2+, DO2-(37, 38). These two digital
outputs can be used as an energy pulse output or over limit alarming output.
The digital output circuit form is Photo-MOS. The simplified circuit is in fig 2.30.
Fig 2.30 Digital output Circuit
The Max output voltage and current are 100V and 50mA.
When the digital output is used as pulse output, DO1 and DO2 can be
Fig 2.30 Digital output Circuit
Power
Supply
Acuvim-X
Photo -Mos
Summary of Contents for XPQ
Page 1: ...POWER INSTRUMENTS DPMS XPQ Multi Function Power Meter User Manual 1087 332...
Page 2: ......
Page 7: ...Chapter 1 Introduction Purpose Application Area Functions DPMS XPQ Series 5...
Page 13: ...Chapter 2 Installation Appearance and Dimensions Installation Method Wiring 11...
Page 30: ...28 DPMS XPQ User Manual 6 2LL 2CT Fig 2 23 2LL 2CT 7 2LL 1CT Fig 2 24 2LL 1CT...
Page 59: ...Chapter 4 Function and Software Functionality and Utility Software 57...
Page 68: ...66 DPMS XPQ User Manual Here is an example Fig 4 7 Demand Here is to set demand...
Page 90: ...88 DPMS XPQ User Manual Fig 4 20 Voltage Eligibility Ratio...
Page 126: ...124 DPMS XPQ User Manual...
Page 127: ...125 Appendix Appendix A Technical Data and Specifications Appendix B Ordering Information...
Page 133: ......