Fig 2.8 Wiring of Power Supply
A fuse (typical 1A/250Vac) should be used in the auxiliary power supply
loop. No.24 terminal must be connected to the safety earth system of
switchgear. An isolated transformer or EMI filter should be used in the auxiliary
power supply loop if there is a power quality problem in the power supply.
Fig 2.9 Wiring of Aux. Power Supply with power line filter
Choice of wire should be AWG22~16 or 0.6~1.3mm
2
.
Note:
A filter should be used if there is an EMI problem.
Voltage Input
Meter input voltage should be 40~230Vac L-N,
60~400Vac. L-L. The voltage input could be directly
connected to the meter terminal without the use of PT if
the voltage system is less than 400Vac (L-L). If the input
Voltage is higher than 400Vac, a PT or VT should be
Note
The secondary of PT
can not be shorted,
otherwise it may cause
the severe damage of
the instrument.
Note
Make sure the power
supply voltage is the
same as what the meter
needs for its auxiliary
power.
L
N Acuvim-X
G
20
22
24
Power Supply
1A FUSE
Ground
L
N Acuvim-X
G
20
22
24
L L
N N
G G
Power Supply
1A FUSE
Ground
Power
filter
Summary of Contents for XPQ
Page 1: ...POWER INSTRUMENTS DPMS XPQ Multi Function Power Meter User Manual 1087 332...
Page 2: ......
Page 7: ...Chapter 1 Introduction Purpose Application Area Functions DPMS XPQ Series 5...
Page 13: ...Chapter 2 Installation Appearance and Dimensions Installation Method Wiring 11...
Page 30: ...28 DPMS XPQ User Manual 6 2LL 2CT Fig 2 23 2LL 2CT 7 2LL 1CT Fig 2 24 2LL 1CT...
Page 59: ...Chapter 4 Function and Software Functionality and Utility Software 57...
Page 68: ...66 DPMS XPQ User Manual Here is an example Fig 4 7 Demand Here is to set demand...
Page 90: ...88 DPMS XPQ User Manual Fig 4 20 Voltage Eligibility Ratio...
Page 126: ...124 DPMS XPQ User Manual...
Page 127: ...125 Appendix Appendix A Technical Data and Specifications Appendix B Ordering Information...
Page 133: ......