73
POWER INSTRUMENTS
Fig 4.13 TOU Schedules Setting
Pulse Energy Output
The two digital outputs can be used as energy pulse output and cannot
be used as the alarming outputs at the same time. The output energy can be
selected among all kinds of energy and reactive energy. Pulse constant and
pulse width can be set to meet your requirements. Pulse constant is the kWh
a pulse stands for, pulse width is the pulse duration. When the accumulated
energy reaches the pulse constant, there will be a pulse on DO.
Related parameters: pulse energy output ranges from 0 to 4 corresponding
to none, Ep_imp, Ep_exp, Eq_imp, Eq_exp.
Pulse constant ranges from 1 - 6000 (integer) with a unit of 0.1kWh (kVARh),
apparently that is the resolving power of energy output.