74
DPMS XPQ User Manual
Pulse width ranges from 1 - 50 (integer) with a unit of 20ms. The narrowest
interval between two pulses is 20ms.
In practice the pulse width and the pulse ratio are selected according to
system power. The relation of the two parameters should be satisfied by the
following expression,
In the expression, the Pmax is the maximum power or reactive power. The
unit is kW or kVAR. Recommend pulse ratio is 3 to 5 times the right side value
of the above expression.
The related settings are:
Fig 4.14 Digital I/O Setting
18000000
Pmax
)
1
width
pulse
(
radio
Pulse
×
+
>