113
POWER INSTRUMENTS
32D6H,32D7H Day: eligible time of three
phase
0.0~3.438
F24
32D8H~32E1H month: same as day
0.0~3.438
F24
32E2H~32EBH Year: same as day
0.0~3.438
F24
32ECH~32F5H Accumulation: same as day
0.0~3.438
F24
The following are statistics of Voltage Eligibility
32F6H,32F7H
Day: eligibility of UA(UAB)
0~1000000000
F23
32F8H,32F9H
Day: eligibility of UB(UBC)
0~1000000000
F23
32FAH,32FBH Day: eligibility of UC(UCA)
0~1000000000
F23
32FCH,32FDH Day: eligibility of three phase
0~1000000000
F23
32FEH~3305H month: same as day
0~1000000000
F23
3306H~330DH Year: same as day
0~1000000000
F23
330EH~3314H Accumulation: same as day
0~1000000000
F23
Freezing Zone:
Real time data will cover the freezing zone after voltage eligibility is frozen
while real time measurement keeps going on. The address range is 316H~
335dH.You can use the 03H function to read it.
Statistics Zone:
When the day changes, the data of real time measurement will be stored in
the statistics zone. The “day” data will clear and restart.
Address
Parameter
Range
Format code
The following are statistics including running time and eligible time
335EH,335FH Day: running time
0.0~3.438
F24
3360H,3361H Day: eligible time of UA(UAB)
0.0~3.438
F24
3362H,3363H Day: eligible time of UB(UBC)
0.0~3.438
F24
3364H,3365H Day: eligible time of UC(UCA)
0.0~3.438
F24
3366H,3367H
Day: eligible time of three phase 0.0~3.438
F24
3368H~3371H month: same as day
0.0~3.438
F24
Summary of Contents for XPQ
Page 1: ...POWER INSTRUMENTS DPMS XPQ Multi Function Power Meter User Manual 1087 332...
Page 2: ......
Page 7: ...Chapter 1 Introduction Purpose Application Area Functions DPMS XPQ Series 5...
Page 13: ...Chapter 2 Installation Appearance and Dimensions Installation Method Wiring 11...
Page 30: ...28 DPMS XPQ User Manual 6 2LL 2CT Fig 2 23 2LL 2CT 7 2LL 1CT Fig 2 24 2LL 1CT...
Page 59: ...Chapter 4 Function and Software Functionality and Utility Software 57...
Page 68: ...66 DPMS XPQ User Manual Here is an example Fig 4 7 Demand Here is to set demand...
Page 90: ...88 DPMS XPQ User Manual Fig 4 20 Voltage Eligibility Ratio...
Page 126: ...124 DPMS XPQ User Manual...
Page 127: ...125 Appendix Appendix A Technical Data and Specifications Appendix B Ordering Information...
Page 133: ......