UNIT N. 2 BLOCK GENERAL ALARM
Display label meaning
ALc2
Cause of activation
With AL56 = 0 ID configured unit n° 2 signal alarm active after the time set in
the Par. AL58
Reset
ID configured as unit n° 2 block signalling alarm not active for the time set in
the Par. AL59
Reset
always automatic
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Other loads
They follow their regulation
Display label meaning
ALc2
Cause of activation
With AL56 = 1 ID configured unit n° 2 block alarm active after the time set in
the Par. AL58
Reset
ID configured as unit n° 2 general block alarm not active for the time set in
the Par. AL59
Reset
If AL51 = 0 always manual
If AL51
!
0 automatic – becomes manual after AL57 interventions/hour (reset
procedure in functions menu) It is recorded in the historical alarms only with
manual reset
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Other loads
Off