Allows maintenance of the circuit
•
Allows "partialised" working of the unit
Possibility of enabling/disabling the individual compressor
•
Maintenance of the individual compressor
•
Malfunction
Complete management of pump down function:
•
With dedicated pressure switch
•
Timed
•
Via the low pressure switch
•
Via the low pressure transducer
Circuit unloading function:
•
From evaporator inlet high water temperature
•
From condenser inlet high water temperature (unit with heat recovery) – Not Available
•
From high condensing pressure
•
From low evaporating pressure
Controlled loads maintenance signal function:
•
Compressors
•
Evaporator pumps
•
Condenser pump
Circuit auxiliary relay function:
•
Four completely configurable relay outputs, also released from normal working of the unit controlled,
managed by means of NTC or PTC temperature probes or with 4÷20mA – 0.5 Volt pressure transducer
Weekly working in energy saving mode:
•
Up to three daily time bands (devices with RTC option)
•
From digital input
Weekly working with automatic switch on and switch off:
•
Up to three daily time bands (devices with RTC option)
Dynamic set-point function:
•
Managed by NTC or 4÷20mA input
Changeover function:
•
Automatic changeover between cooling and heating by NTC input
Remote OFF function:
•
From configurable digital input
Remote heating cooling function:
•
From digital input with configurable logic
Hot start function:
•
Air/air unit
Defrost management:
•
In temperature in pressure or with both (combined control)
•
Forced defrost for start-up with low external air temperatures
•
From digital input or timed
•
Manual using the relevant key
Boiler function:
•
With integration heaters
N° 2 outputs for the proportional control of the condensing fan speeds via external module (inverter
or single/three phase phase cut) with configurable signal:
•
PWM
•
0÷10 Volt
•
4÷20 mA
N° 6 outputs for 0÷10V proportional or ON/OFF control
•
To control the servomotors working in free cooling or heat recovery mode
•
For driving an external relay
Complete alarms management
•
With internal data logger alarms (up to 100 events)
Up to n° 2 programmable remote LCD terminals with customisable values display
•
with NTC probe on board for room temperature display and temperature control (Not Available).
Supervision/tele-assistance/remote monitoring
for complete control and supervision from local and
remote
•
By means of network output with ModBus TCP / IP protocol (INTERNET / INTRANET)
•
Directly by telephone line (MODEL WITH INTERNAL MODEM)
•
Indirectly by means of GSM modem or XWEB serial modem (MODEL WITH RS232 OUTPUT
PREPARATION)