USER MANUAL – Release 1.2 of 01/01/2010
Page 169 of 191
Version: 02/03/2010
57.18
DISCHARGE COMPRESSORS HIGH TEMPERATURE ALARM FROM
ANALOGUE INPUT
Display label meaning
C1dt
…
C16dt
(compressor n° 1…16 high discharge temperature alarm)
Cause of activation
The temperature measured by the probe configured as discharge high
temperature > AL50 set
Reset
The temperature measured by the probe configured as discharge high
temperature < AL50 set – AL51 differential
Reset
Automatic Manual. If more than AL52 interventions per hour occur. Enter the
functions menu to reset the alarm
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Reverse valve
it follows its regulation
Recovery valve
it follows its regulation
Free-cooling on/off valve
it follows its regulation
Auxiliary relay
It follows its regulation
Idle running valve
It follows its regulation
Supply ventilation
It follows its regulation
Condensation ventilation
It follows its regulation
Support/boiler/anti-freeze
It follows/they follow its/their regulation
Pump/and water evaporator
and condenser
It follows its regulation
Compressor affected
Off
Compressor not affected
It follows its regulation
Pump down solenoid valve It switches-off if there is only 1 compressor per circuit, otherwise it follows its
regulation
Liquid injection solenoid
valve
Off with compressor in OFF
57.19
EVAPORATOR WATER INLET HIGH TEMPERATURE ALARM
Display label meaning
AEht
(evaporator water inlet high temperature alarm)
Cause of activation
During cooling mode, the temperature measured by the probe configured in
AL64 > AL62 set
Reset
The temperature measured by the probe configured in AL64 < AL62 set –
AL63 differential
Reset
Reset is always manual if AL60 = 0
Reset is always automatic if AL60 = 16
Reset passes from automatic to manual if AL60 goes from 1 to 15
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Compressors
Off
Other loads
It follows its regulation
WARNING:
The alarm only appears if the unit is running with compressor on after time
AL61
.