57.8
LOW CONDENSATION TEMPERATURE/PRESSURE (IF THE LOW PRESSURE
TRANSDUCERS ARE NOT USED)
Display label meaning
b1lP
(circuit n° 1 analogue input low pressure)
b2lP
(circuit n° 2 analogue input low pressure)
b3lP
(circuit n° 3 analogue input low pressure)
b4lP
(circuit n° 4 analogue input low pressure)
Cause of activation
The alarm is activated when the probe configures as the condensation control
measures a temperature < AL03 set in the following conditions:
•
working in cooling or heating mode
•
stand-by or OFF-remote if AL08 = 1
!
In defrost if AL06=1
The alarm is not signalled:
•
in defrost for time AL07 in correspondence with valve inversion
•
on compressor switch-on for the time AL01
Reset
If the condensation control probe measures a set temperature > AL03 +
differential AL04
Reset
Automatic – it becomes manual after AL05 interventions/hour (reset procedure
in functions menu)
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Reverse valve
it follows its regulation
Recovery valve
it follows its regulation
Free-cooling on/off valve
it follows its regulation
Auxiliary relay
It follows/they follow its/their regulation
Idle running valve
It follows its regulation
Supply ventilation
It follows its regulation
Condensation ventilation
Off
Support/boiler/anti-freeze
It follows its regulation
Pump/and water evaporator
and condenser
It follows its regulation
Compressors
Off
Pump down solenoid valve off